| 2002-04-05 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | |
| | 1) FBC 1004.1.2NUMBER AND ARRANGEMENT |
| | OF EXITS.EVERY ROOM OR TENANT SPACE IN |
| | WHICH THE TRAVEL DISTANCE FROM THE MOST |
| | REMOTE POINT TO THE EXIT ACCESS EXCEEDS |
| | 75 FEET SHALL HAVE NOT LESS THAN TWO |
| | EGRESS DOORS.THE TRAVEL DISTANCE FROM |
| | THE CORNER OF OFFICE 1 IS ALREADY CLOSE |
| | TO 75 FEET WITHOUT TAKING INTO ACCOUNT |
| | ANY FURNITURE OR OTHER OBSTRUCTIONS. |
| | SUBMIT FURNITURE PLANS FOR OFFICE 1, |
| | 'WORK AREA' AND RECEPTION SHOWING THAT |
| | THE TRAVEL DISTANCE FROM THE CORNER OF |
| | OFFICE 1 TO THE TENANT EXIT ACCESS DOOR |
| | DOES NOT EXCEED 75 FEET.NOTE THAT IF |
| | TWO EXIT ACCESS DOORS ARE REQUIRED, THEY |
| | MUST BE SEPARATED BY A DISTANCE EQUAL TO |
| | NOT LESS THAN 1/2 OF THE MAXIMUM OVERALL |
| | DIAGONAL OF THE TENANT SPACE. |
| | |
| | 2) FBC 2405.2 THE SIDE LIGHT GLAZING IS |
| | IN A 'HAZARDOUS LOCATION' AND IS |
| | REQUIRED TO BE SAFETY GLASS SATISFYING |
| | THE REQUIREMENTS OF THE CONSUMER PRODUCT |
| | SAFETY COMMISSION 16, CODE OF FEDERAL |
| | REGULATIONS, PART 1201 (CPSC 16-CFR, |
| | PART 1201).SUBMIT DETAILS TO |
| | DEMONSTRATE COMPLIANCE. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |
| | THE CODE REFERENCES GIVE ADDITIONAL INFO |
| | IF YOU HAVE ANY QUERIES PLEASE CALL: |