2002-04-04 00:00:00A) PLEASE BE ADVISED THAT THE DRAWINGS
 SUBMITTED ARE NOT REVISIONAL. THE
 NEW EQUIPMENT AND DEVICES WERE NOT SHOWN
 ON THE FIRE SPRINKLER PERMIT THAT WAS
 APPROVED. PLEASE SUBMIT A PERMIT
 APPLICATION FOR THE NEW DRAWINGS AFTER
 THEY ARE CORRECTED.
 B) THE FIRE HYDRANT SHOWN DOES NOT
 MEET CITY STANDARDS. ALSO THE FIRE
 HYDRANT VALVE SHOULD BE NOT MORE THAN
 FOUR FEET FROM THE FIRE HYDRANT.
 C) ALL NEW PIPING IS TO BE PRESSURE
 TESTED AT 200 PSI FOR TWO HOURS.
 D) THE NEW FIRE HYDRANT SHALL PROVIDE
 AT LEAST 7' - 6" TO THE FRONT AND SIDES
 AND 4' TO THE REAR.
 E) A MINIMUM OF 7' - 6" IS TO BE
 PROVIDED FOR FIRE PROTECTION APPLIANCES.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL