| Plan Review Notes For Permit 02030583 |
| Permit Number |
02030583 |
|
| Review Stop |
FS |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2002-04-04 00:00:00 | A) PLEASE BE ADVISED THAT THE DRAWINGS | | | SUBMITTED ARE NOT REVISIONAL. THE | | | NEW EQUIPMENT AND DEVICES WERE NOT SHOWN | | | ON THE FIRE SPRINKLER PERMIT THAT WAS | | | APPROVED. PLEASE SUBMIT A PERMIT | | | APPLICATION FOR THE NEW DRAWINGS AFTER | | | THEY ARE CORRECTED. | | | B) THE FIRE HYDRANT SHOWN DOES NOT | | | MEET CITY STANDARDS. ALSO THE FIRE | | | HYDRANT VALVE SHOULD BE NOT MORE THAN | | | FOUR FEET FROM THE FIRE HYDRANT. | | | C) ALL NEW PIPING IS TO BE PRESSURE | | | TESTED AT 200 PSI FOR TWO HOURS. | | | D) THE NEW FIRE HYDRANT SHALL PROVIDE | | | AT LEAST 7' - 6" TO THE FRONT AND SIDES | | | AND 4' TO THE REAR. | | | E) A MINIMUM OF 7' - 6" IS TO BE | | | PROVIDED FOR FIRE PROTECTION APPLIANCES. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|