Plan Review Notes For Permit 02030574
Permit Number 02030574
Review Stop B
Sequence Number 5
Notes
Date Text
2002-07-08 00:00:00THE INFORMATION ON THE "REDDI-FORM
 SYSTEM" WAS PREVIOUSLY REQUESTED TWICE.
 IT IS STILL ABSENT.
  
 THE PLANS RESUBMITTED 6/19/02 UNDER THE
 SEAL AND SIGNATURE OF WALTER KARPINIA,
 PE, DO NOT HAVE ENOUGH STRUCTURAL
 DETAILS.
  
 SHEET A1 DECLARES ON THE FOUNDATION
 PLANA - 10" POST AND BEAM STRUCTURAL
 SYSTEM AS PER REDDI-FORM STAY IN PLACE
 INSULATED WALL SYSTEM.SEE CHAPTER
 61G15-31 RESPONSIBILITY RULES OF
 PROFESSIONAL ENGINEERS CONCERNING THE
 DESIGN OF STRUCTURES.WITH REGARDS TO
 DELEGATED DESIGN RESPONSIBILTY AND
 GENERAL RESPONSIBILITY.
  
 THE THICKNESS OF THE CONCRETE AND THE
 INSULATION IS NOT SHOWN.HOW IS THE
 INSULATION ADDRESSED WHEN THE VARIOUS
 STRUCTURAL COMPONENTS ARE ATTACHED TO
 THE WALL?
  
 SHEET A2 DECLARES #5 VERT @ 12" OC AND
 #5 HORIZ @ 48" OC.THERE ARE NO
 DETAILS FOR CORNERS, FOUNDATION
 CONNECTION, OR INTERUPTION AT OPENINGS.
  
 PROVIDE AN EVALUATION REPORT LISTING
 FOR THE SIMPSON ICFLC/ICFLC-W LEDGER
 BRACKETS.
  
 SHEET A3 WHAT IS THE EMBED DEPTH OF THE
 5/8" BOLT FOR THE LEDGER SUPPORTING THE
 PORCH ROOF?
  
 THE BUILDING CODE IN EFFECT IS THE FBC
 NOT SBCCI.