| Plan Review Notes For Permit 02030574 |
| Permit Number |
02030574 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2002-05-21 00:00:00 | THE MINIMUM DESIGN PRESSURE ON SHEET | | | A-3DOES NOT MAKE SENSE. BOTH THE | | | INTERNAL PRESSURE COEFFICENT AND | | | COMPONENT DECLARE 16.1/ -30.2. | | | | | | | | | INFORMATION PREVIOUSLY REQUESTED FOR THE | | | "REDI FORMSYSTEM" HAS NOT BEEN | | | PROVIDED. IF THE WALLS ARE TO BE OF | | | REINFORCED CONCRETE PROVIDE A DESIGN BY | | | A STRUCTURAL ENGINEER DEMONSTRATING | | | COMPLIANCE WITH FBC 1901.1.2. | | | | | | THE SPECIFICATION FOR THE LAMINATED | | | LUMBER HAS NOT BEEN PROVIDED.SEE FBC | | | 2301.2.5. | | | | | | THE PLANS MUST BE REVIEWED BY THE COUNTY | | | FOR IMPACT FEES.CALL 233-5025 FOR | | | MORE INFORMATION. |
|