| Plan Review Notes For Permit 02030574 |
| Permit Number |
02030574 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-05-13 00:00:00 | ***************** UNSAT ************** | | | | | | 1)NOTE: PLEASE NOTE , NOW A RISER | | | DIAGRAM IS SUBMITTED AND SHOWS A NEW | | | 100A FEED FROM EXISTING PANEL?? | | | PLEASE NOTE, NO INFORMATION WAS GIVEN | | | FOR EXISTING PANEL, SIZE? PLEASE | | | SUBMIT A LOAD CALCUALTION, NOW THAT YOU | | | SHOW ADDING A NEW LOAD OF 98AMPS? | | | 215-5 | | | | | | 2)NOTE: PLEASE NOTE MISSING EQUIPMENT | | | GROUNDING CONDUCTOR BETWEEN EXIST PANEL | | | AND DETACHED BLDG.250-32 SIZE PER 250- | | | 122. | | | | | | 3)NOTE: PLEASE NOTE PLANS NOW SHOW A NEW | | | PANEL, PLEASE SHOW AIC RATING FOR NEW | | | EQUIPMENT.110-9 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | '561-659-8096 EXT 8372 |
|