Plan Review Notes
Plan Review Notes For Permit 02030574
Permit Number 02030574
Review Stop E
Sequence Number 2
Notes
Date Text
2002-05-13 00:00:00***************** UNSAT **************
  
 1)NOTE: PLEASE NOTE , NOW A RISER
 DIAGRAM IS SUBMITTED AND SHOWS A NEW
 100A FEED FROM EXISTING PANEL??
 PLEASE NOTE, NO INFORMATION WAS GIVEN
 FOR EXISTING PANEL, SIZE? PLEASE
 SUBMIT A LOAD CALCUALTION, NOW THAT YOU
 SHOW ADDING A NEW LOAD OF 98AMPS?
 215-5
  
 2)NOTE: PLEASE NOTE MISSING EQUIPMENT
 GROUNDING CONDUCTOR BETWEEN EXIST PANEL
 AND DETACHED BLDG.250-32 SIZE PER 250-
 122.
  
 3)NOTE: PLEASE NOTE PLANS NOW SHOW A NEW
 PANEL, PLEASE SHOW AIC RATING FOR NEW
 EQUIPMENT.110-9
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 '561-659-8096 EXT 8372