| 2002-04-16 00:00:00 | BEFORE A PERMIT TO CONSTRUCT MAY BE |
| | ISSUED IMPACT FEES MUST BE PAID TO THE |
| | COUNTY FOR THE CITY, THE PERMIT PLANS |
| | STAMPED BY THAT OFFICE AND A COPY OF |
| | THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION.CALL 233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | SHOW THE DESIGN WINDLOAD INFORMATION ON |
| | THE PLANS IN ACCORDANCE WITH FBC 1606.1. |
| | 7. |
| | |
| | PROVIDE INFORMATION ON THE "REDDI FORM" |
| | WALL SYSTEM TO BE USED.IS THIS THE |
| | "INSULATED CONCRETE FORM" DESCRIBED IN |
| | FBC 1916?IF SO SEE THOSE LIMITATIONS. |
| | |
| | PLEASE PROVIDE A VALID SIGNED AND |
| | SEALEDSURVEY. |
| | |
| | DECLARE THE USE OF THE LOFT. |
| | |
| | SHOW THE FINISH FLOOR ELEVATION. |
| | |
| | SPECIFY THE MINMUM GRADE AND SPECIES FOR |
| | THE FRAMING LUMBER.SPECIFY THE DESIGN |
| | INFORMATION FOR THE LAMINATED TIMBER. |
| | |
| | PROVIDE A LOADING ANALYSIS FOR THE |
| | LUMBER AT THE 5/8" BOLT SHOWN SPACED |
| | 36" O.C.CARRYING THE LOFT. |
| | |
| | SPECIFY THE APPROPRIATE ANCHOR FOR THE |
| | LAMINATED LUMBER. |
| | |
| | PROVIDE A MORE SPECIFIC DETAIL FOR THE |
| | CONNECTION OF THE 6X6 CYPRESS POSTS TO |
| | THE BEAM AND FOOTING. |
| | |
| | SHOW THE CONNECTION FOR THE ROOF TRUSSES |
| | TO THE WALL, OR THE LOCATION, NATURE, |
| | DIRECTION AND MAGNITUDE OF THE FORCES |
| | TO BE RESISTED. |
| | |
| | SHOW THE ATTIC VENTILATION AND ACCESS IN |
| | ACCORDANCE WITH FBC 2309.6 AND 2309.7. |
| | |
| | PROVIDE ADDITIONAL DIMENSIONS TO LOCATE |
| | THE FOOTING PADS ON THE SOUTH ELEVATION |
| | FOR THE COVERED LOGGIA. |
| | |
| | PROVIDE CALCULATIONS FOR THE |
| | CANTILEVERED 6X8 CYPRESS BEAMS AT THE |
| | SOUTH WEST CORNER OF THE LOGGIA. |