| Plan Review Notes For Permit 02030574 |
| Permit Number |
02030574 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-03-27 00:00:00 | DENIED | | | REFERENCE: FBC-2001 | | | | | | 1) SHT A-1 PLUMBING RISER DIAGRAM. EVERY | | | SANITARY DRAINAGE SYSTEM RECIEVING DIS- | | | CHARGE OF A WATER CLOSET SHALL HAVE A | | | MAIN VENT. SUCH VENT SHALL RUN UNDIMIN- | | | ISHED IN SIZE AND AS DIRECTLY AS POSSIB- | | | LE FROM DRAIN TO OPEN AIR ABOVE THE ROOF | | | SEC 903.1 | | | 2) SHT A-1 NOTES #1 DRAIN LINES 2-1/2" | | | AND SMALLER SHALL SLOPE AT 1/4" PER FOOT | | | MINIMUM. TABLE 704.1 | | | 3) SHT A-1 DISHWASHER NOT TRAPPED AS | | | SHOWN. DISHWASHER SHALL DRAIN INTO BAR | | | SINK TAILPIECE NOT THRU FLOOR INTO BLDG | | | DRAIN. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|