Plan Review Notes For Permit 02030574
Permit Number 02030574
Review Stop P
Sequence Number 1
Notes
Date Text
2002-03-27 00:00:00DENIED
 REFERENCE: FBC-2001
  
 1) SHT A-1 PLUMBING RISER DIAGRAM. EVERY
 SANITARY DRAINAGE SYSTEM RECIEVING DIS-
 CHARGE OF A WATER CLOSET SHALL HAVE A
 MAIN VENT. SUCH VENT SHALL RUN UNDIMIN-
 ISHED IN SIZE AND AS DIRECTLY AS POSSIB-
 LE FROM DRAIN TO OPEN AIR ABOVE THE ROOF
 SEC 903.1
 2) SHT A-1 NOTES #1 DRAIN LINES 2-1/2"
 AND SMALLER SHALL SLOPE AT 1/4" PER FOOT
 MINIMUM. TABLE 704.1
 3) SHT A-1 DISHWASHER NOT TRAPPED AS
 SHOWN. DISHWASHER SHALL DRAIN INTO BAR
 SINK TAILPIECE NOT THRU FLOOR INTO BLDG
 DRAIN.
  