| 2002-03-15 00:00:00 | ****************** UNSAT ************* |
| | |
| | 1)NOTE: |
| | |
| | |
| | |
| | |
| | 2)NOTE: PLEASE NOTE PLAN FOR ELECTRICAL |
| | IS NOT COMPLETE. PLEASE NOTE THAT NO |
| | RISER DIAGRAM WAS SUBMITTED TO SHOW |
| | WHERE/HOW THE NEW CABANA IS GETTING |
| | ELECTRIC?? |
| | PLEASE NOTE ,,PANEL(S), DISCONNECT, |
| | GROUNDING, WIRE, CONDUIT SIZES ETC. |
| | |
| | 3)NOTE: PLEASE NOTE MISSING SMOKE |
| | DETECTOR ON LOWER LEVEL OF STAIRS. |
| | NFPA-72 2-2.1.1.1, 2-5.2.1.3. |
| | |
| | 4) NOTE: PLEASE LIST THE REQ`D BATH(S) |
| | CIRCUIT(S) PER 210-11-C-3. |
| | MUST BE 20A AND #12AWG. |
| | |
| | 5) NOTE: PLEASE SHOW ALL OUTLET SPACING |
| | TO MEET 2`,6`,12` RULE PER 210-52. |
| | MISSING FOR SECOND FLOOR GUARD RAIL. |
| | THIS IS CONSIDERED WALL SPACE. (FLOOR |
| | BOX). |
| | |
| | 6) PLEASE NOTE MISSING OUTLET FOR A/C |
| | EQUIPMENT PER 210-63 OF NEC AND 309.2 |
| | MECHANICAL CODE. |
| | |
| | 7) PLEASE NOTE EITHER MISSING EGRESS |
| | LIGHTING AND/OR CLARIFY EGRESS LIGHTING |
| | PER 210-70 OF THE NEC. |
| | ATLEAST ONE LT FOR EGRESS TO OUTSIDE. |
| | BOTH LOCATIONS SHOWN AS "J" BOX NOW. |
| | |
| | 8)NOTE: PLEASE NOTE OUTLETS IN GARAGE TO |
| | BE SHOWN AS GFI/GFI PROTECTED. |
| | |
| | 9)NOTE: PLEASE NOTE THAT AREA CAN ALSO |
| | BE USED AS SLEEPING/. PLEASE LIST ARC |
| | FAULT PROTECTION PER 210-12. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |