Plan Review Notes
Plan Review Notes For Permit 02030574
Permit Number 02030574
Review Stop E
Sequence Number 1
Notes
Date Text
2002-03-15 00:00:00****************** UNSAT *************
  
 1)NOTE:
  
  
  
  
 2)NOTE: PLEASE NOTE PLAN FOR ELECTRICAL
 IS NOT COMPLETE. PLEASE NOTE THAT NO
 RISER DIAGRAM WAS SUBMITTED TO SHOW
 WHERE/HOW THE NEW CABANA IS GETTING
 ELECTRIC??
 PLEASE NOTE ,,PANEL(S), DISCONNECT,
 GROUNDING, WIRE, CONDUIT SIZES ETC.
  
 3)NOTE: PLEASE NOTE MISSING SMOKE
 DETECTOR ON LOWER LEVEL OF STAIRS.
 NFPA-72 2-2.1.1.1, 2-5.2.1.3.
  
 4) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 5) NOTE: PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
 MISSING FOR SECOND FLOOR GUARD RAIL.
 THIS IS CONSIDERED WALL SPACE. (FLOOR
 BOX).
  
 6) PLEASE NOTE MISSING OUTLET FOR A/C
 EQUIPMENT PER 210-63 OF NEC AND 309.2
 MECHANICAL CODE.
  
 7) PLEASE NOTE EITHER MISSING EGRESS
 LIGHTING AND/OR CLARIFY EGRESS LIGHTING
 PER 210-70 OF THE NEC.
 ATLEAST ONE LT FOR EGRESS TO OUTSIDE.
 BOTH LOCATIONS SHOWN AS "J" BOX NOW.
  
 8)NOTE: PLEASE NOTE OUTLETS IN GARAGE TO
 BE SHOWN AS GFI/GFI PROTECTED.
  
 9)NOTE: PLEASE NOTE THAT AREA CAN ALSO
 BE USED AS SLEEPING/. PLEASE LIST ARC
 FAULT PROTECTION PER 210-12.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  