Plan Review Notes
Plan Review Notes For Permit 02030460
Permit Number 02030460
Review Stop M
Sequence Number 1
Notes
Date Text
2002-03-07 00:00:00 
 PLEASE NOTE NEW 2001 FLORIDA BUIDLING
 CODE IN EFFECT AS OF MARCH 1, 2002.
  
 PROVISO:
  
 AS PER 2001 FBC, MECHANICAL 601.4 -
 BALANCED AIR RETURN REQUIRED.PRESSURE
 DIFFERENTIALS ACROSS CLOSED DOORS WHERE
 RETURNS ARE CENTRALLY LOCATED SHALL BE
 LIMITED TO .001 INCH WC OR LESS.
 PROVIDE AIR DUCT PATHWAYS OR AIR
 TRANSFER PATHWAYS FROM THE HIGH
 PRESSURE ZONE TO THE LOW PRESSURE ZONE.
  
 OUTSIDE AIR REQUIRED AS PER 2001 FBC,
 MECH 403.3.
  
 BATHROOM SHALL BE MECHANICALLY
 EXHAUSTED AS PER 2001 FBC MECH 402.3.1.