| 2002-04-23 00:00:00 | DRAWING #0089 IS ILLEGIBLE AND THE | | | COMPONENTS ARE NOT PROPERLY MARKED. | | | REFER TO SBCCI REPORT 9857.NOTE ALSO | | | THE "SPECIAL INSPECTION" REQUIRED BY | | | THAT REPORT. | | | | | | THE REPORT FAXED TO ME 4/16/02 IS A POOR | | | REPRODUCTION.THE DRAWING #98-156 | | | CITEE IN THE REPORT WAS NOT INCLUDED. | | | ASSUMING DWG. #00-271 IS A VALID | | | SUBSTITUTE, THE COMPONENTS AND | | | FASTENERS ARE NOT PROPERLY SELECTED AND | | | "SPECIAL INSPECTION" IS REQUIRED ALSO. |
|