| Plan Review Notes For Permit 02030430 |
| Permit Number |
02030430 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2002-05-13 00:00:00 | WHICH SHUTTER TYPE WAS USED FOR THIS | | | INSTALLATION?ECONOMY OR RESIDENTIAL? | | | | | | THE SBCCI REPORT PROVIDED, #2127, | | | REQUIRES THAT THE FASTENER INSTALLATION | | | HAVE A "SPECIAL INSPECTION".SINCE THE | | | SHUTTERS HAVE BEEN INSTALLED WITHOUT | | | BENFIT OF A PERMIT, PROVIDE A WRITTEN | | | REPORT FROM THE SPECIAL INSPECTOR, | | | INCLUDING THE INSPECTOR'S | | | QUALIFICATIONS AS DEFINED IN SECTION | | | 5.2 OF THE SBCCI REPORT. | | | | | | REPORT # 2127 REFERENCES DWG #98-59 FOR | | | ECONOMY SHUTTERS AND #98-156 FOR | | | RESIDENTIAL SHUTTERS.NEITHER OF THESE | | | DRAWINGS HAVE BEEN PROVIDED IN | | | ACCORDANCE WITH THE REPORT. | | | | | | THE PRINTED SHEET TITLED "ACCORDIONS" IS | | | NOT COMPLETE IN ITS DESCRIPTION IF IT | | | IS INTENDED TO DEFINE THE COMPONENTS | | | USED. |
|