Plan Review Notes
Plan Review Notes For Permit 02030430
Permit Number 02030430
Review Stop B
Sequence Number 3
Notes
Date Text
2002-05-13 00:00:00WHICH SHUTTER TYPE WAS USED FOR THIS
 INSTALLATION?ECONOMY OR RESIDENTIAL?
  
 THE SBCCI REPORT PROVIDED, #2127,
 REQUIRES THAT THE FASTENER INSTALLATION
 HAVE A "SPECIAL INSPECTION".SINCE THE
 SHUTTERS HAVE BEEN INSTALLED WITHOUT
 BENFIT OF A PERMIT, PROVIDE A WRITTEN
 REPORT FROM THE SPECIAL INSPECTOR,
 INCLUDING THE INSPECTOR'S
 QUALIFICATIONS AS DEFINED IN SECTION
 5.2 OF THE SBCCI REPORT.
  
 REPORT # 2127 REFERENCES DWG #98-59 FOR
 ECONOMY SHUTTERS AND #98-156 FOR
 RESIDENTIAL SHUTTERS.NEITHER OF THESE
 DRAWINGS HAVE BEEN PROVIDED IN
 ACCORDANCE WITH THE REPORT.
  
 THE PRINTED SHEET TITLED "ACCORDIONS" IS
 NOT COMPLETE IN ITS DESCRIPTION IF IT
 IS INTENDED TO DEFINE THE COMPONENTS
 USED.