2 |
|
| Notes |
| Date |
Text |
| 2002-06-20 00:00:00 | REVISION MECHANICAL PERMIT 02030143 | | | | | | CONDENSATE SHALL DISCHARGE A MINIMUM OF | | | 12" AWAY FROM THE BUILDING STRUCTURE AS | | | PER 2001 FBC 1503.4.4. | | | | | | SMOKE DETECTORS SHALL BE INSTALLED | | | SUPPLY SYSTEMS WITH A DESIGN CAPACITY | | | GREATER THAN 2,000 CFM, IN THE SUPPLY | | | AIR DUCT. 2001 FBC(M) 606.2.1OR | | | UPON ACTIVATION, THE SMOKE DETECTORS | | | SHALL SHUTDOWN THE AIR DISTRIBUTION | | | SYSTEM. 2001 FBC(M) 606.4 |
|