| Plan Review Notes For Permit 02022394 |
| Permit Number |
02022394 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-03-08 00:00:00 | ***************** UNSAT ************* | | | | | | 1) NOTE: PLEASE LIST THE REQ`D BATH(S) | | | CIRCUIT(S) PER 210-11-C-3. | | | MUST BE 20A AND #12AWG. | | | | | | 2) NOTE: SMOKE DETECTORS ARE REQUIRED | | | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. | | | ALSO ON EACH LEVEL OF A MULTI-LEVEL | | | DWELLING UNIT. ROOMS WITH BATHS AND OR | | | CLOSETS ARE CONSIDERED SLEEPING ROOMS. | | | PER NFPA-72 2-2.1.1.1. | | | MISSING IN AND OUT BED RM. | | | | | | 3)NOTE: GFI REQ`D FOR SECOND BATH IF NOT | | | EXSITING.210-52D | | | | | | 4) NOTE: PLEASE SHOW ALL OUTLET SPACING | | | TO MEET 2`,6`,12` RULE PER 210-52. | | | WITHIN 6' OF DOOR IN BED RM. | | | | | | 5)NOTE: PLEASE CLARIFY IF NEW WASHER/DRY | | | -ER IS BEING MOVED FROM EXISTING | | | LOCATION? | | | | | | 6)NOTE: PLEASE CLARIFY SIZE OF EXISTING | | | SERVICE. NOTE #3 MENTIONS POSSIBLE NEW | | | SERV? PLEASE SUBMIT. PLEASE SUBMIT A | | | LOAD CALC TO INCLUDE NEW LOADS AND NEW | | | 30A A/C WINDOW UNIT. | | | | | | 7)NOTE: PLEASE NOTE CLOSET LTS DO NOT | | | MEET 410-8. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|