Plan Review Notes
Plan Review Notes For Permit 02022394
Permit Number 02022394
Review Stop E
Sequence Number 1
Notes
Date Text
2002-03-08 00:00:00***************** UNSAT *************
  
 1) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 2) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
 MISSING IN AND OUT BED RM.
  
 3)NOTE: GFI REQ`D FOR SECOND BATH IF NOT
 EXSITING.210-52D
  
 4) NOTE: PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
 WITHIN 6' OF DOOR IN BED RM.
  
 5)NOTE: PLEASE CLARIFY IF NEW WASHER/DRY
 -ER IS BEING MOVED FROM EXISTING
 LOCATION?
  
 6)NOTE: PLEASE CLARIFY SIZE OF EXISTING
 SERVICE. NOTE #3 MENTIONS POSSIBLE NEW
 SERV? PLEASE SUBMIT. PLEASE SUBMIT A
 LOAD CALC TO INCLUDE NEW LOADS AND NEW
 30A A/C WINDOW UNIT.
  
 7)NOTE: PLEASE NOTE CLOSET LTS DO NOT
 MEET 410-8.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372