| 2002-04-02 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT 02022394 |
| | 242 BEVERLY RD |
| | O/B BURKHART, MARGARET |
| | TEL: 582-1618 |
| | |
| | 1) PLANS DO NOT INDICATE AS TO WHICH |
| | CODE THE PLANS WERE DESIGNED TO? |
| | 2) PLANS DO NOT GIVE INFORMATION ON THE |
| | EXISTING STRUCTURE AS TO THE DIRECTION |
| | OF THE ROOF FRAMING MEMBERS? THE SOUTH |
| | END OF THE STRUCTURE HAS 16'-0" OF BLOCK |
| | WALL REMOVED WITH OUT ANY DIRECTION AS |
| | TO THE REINFORCING OF THE CONCRETE BEAM |
| | AND ROOF LOADING OF THE EXISTING STRUC- |
| | TURE PLUS THE ADDTIONAL LOADING FROM THE |
| | NEW LANAI. |
| | 3) THE NEW BEDROOM ADDITION INDICATES A |
| | 10'-0" OPENING WITH OUT ANY REINFORCE- |
| | MENT TO THE NEW CONCRETE BEAM. |
| | 4) THERE IS NO ELEVATIONS TO HELP |
| | IN THE PLAN REVIEW.THE PLAN ALSO INDICAT |
| | ES THAT THE EXISTING SLAB IS TO BE CUT |
| | WITH A NEW FOOTER FOR THE ADDITION? |
| | TERMITE TREATMENTTO THE EXISTING SLAB, |
| | IS IT AT THE CORRECT HEIGTH TO MAKE THE |
| | TRANSITION INTO THE EXISTING STRUCTURE? |
| | 5) THERE IS NO PRODUCT TESTING REPORTS |
| | FOR GLAZED OPENINGS, DOORS, NOR ROOF |
| | COVERINGS? PROVIDE 2 COPIES OF REPORTS |
| | FOR WIND AS WELL AS FOR LARGE MISSLE |
| | IMPACT TESTING. INDICATE THE POSITIVE |
| | & NEGATIVE PRESSURE ZONES THAT WILL |
| | OCCUR ON THE STRUCTURE. |
| | 6) THE PRMIT APPLICATION INDICATES THAT |
| | THE LANAI IS TO BE PART OF THIS PERMIT |
| | APPLICATION, THERE IS NO INFORMATION |
| | ON THE FOOTER NOR PRODUCT INFORMATION |
| | FOR THE SCREEN ENCLOSURE OR PORCH? |
| | 7) THESE PLANS ARE INSUFFICIENT TO COMPL |
| | ETE A COMPENTANT PLAN REVIEW, TO MANY |
| | LOOSE ENDS ON THE PLAN THAT ARE NOT |
| | ADDRESSED!!!!!! |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | (561)659-8096 X8412 |