Plan Review Notes
Plan Review Notes For Permit 02022358
Permit Number 02022358
Review Stop E
Sequence Number 1
Notes
Date Text
2002-04-02 00:00:00**************** UNSAT ***************
  
 1) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
 PLEASE NOTE CLOSE PROXIMITY TO STAIRWAYS
 PER 2-5.2.1.3.
 MISSING TOP AND BOTTOM OF STAIRS AND IN
 DEN.
  
 2) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 3) NOTE: PLEASE SHOW GROUNDING ELECTRODE
 GOING TO BUILDING STEEL AND COLD WATER
 PER 250-50.
 MISSING BLDG/FOOTER STEEL.
  
 4)NOTE: PLEASE CLARIFY LOCATIONS OF
 PANELS/ PLANS SHOW PANELS IN GARAGE,
 BUT DO NOT SHOW MAIN DISC`S? OR GUTTER
 LOCATION. PLEASE SHOW MAINS ON PLANS.
  
 5)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 PROTECTED CIRCUITS PER 210-12 ON PANEL
 SCHEDULE(S).
  
 6)NOTE: PLEASE NOTE MISSING EQUIPMENT
 GROUNDING CONDUCTOR BETWEEN MAIN DISC`S
 AND PANELS. SIZE PER 250-122.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372