| Plan Review Notes For Permit 02022358 |
| Permit Number |
02022358 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-04-02 00:00:00 | **************** UNSAT *************** | | | | | | 1) NOTE: SMOKE DETECTORS ARE REQUIRED | | | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. | | | ALSO ON EACH LEVEL OF A MULTI-LEVEL | | | DWELLING UNIT. ROOMS WITH BATHS AND OR | | | CLOSETS ARE CONSIDERED SLEEPING ROOMS. | | | PER NFPA-72 2-2.1.1.1. | | | PLEASE NOTE CLOSE PROXIMITY TO STAIRWAYS | | | PER 2-5.2.1.3. | | | MISSING TOP AND BOTTOM OF STAIRS AND IN | | | DEN. | | | | | | 2) NOTE: PLEASE LIST THE REQ`D BATH(S) | | | CIRCUIT(S) PER 210-11-C-3. | | | MUST BE 20A AND #12AWG. | | | | | | 3) NOTE: PLEASE SHOW GROUNDING ELECTRODE | | | GOING TO BUILDING STEEL AND COLD WATER | | | PER 250-50. | | | MISSING BLDG/FOOTER STEEL. | | | | | | 4)NOTE: PLEASE CLARIFY LOCATIONS OF | | | PANELS/ PLANS SHOW PANELS IN GARAGE, | | | BUT DO NOT SHOW MAIN DISC`S? OR GUTTER | | | LOCATION. PLEASE SHOW MAINS ON PLANS. | | | | | | 5)NOTE: PLEASE LIST THE REQ`D ARC FAULT | | | PROTECTED CIRCUITS PER 210-12 ON PANEL | | | SCHEDULE(S). | | | | | | 6)NOTE: PLEASE NOTE MISSING EQUIPMENT | | | GROUNDING CONDUCTOR BETWEEN MAIN DISC`S | | | AND PANELS. SIZE PER 250-122. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|