Plan Review Notes
Plan Review Notes For Permit 02022358
Permit Number 02022358
Review Stop B
Sequence Number 1
Notes
Date Text
2002-04-09 00:00:00BUILDING PLAN REVIEW
 PERMIT# 02022358
 2717 SENECA CIRCLE
 CONT SHELTER CONST
 TEL: 687-3600
  
 SBC= 1997 STANDARD BUILDING CODE
 SBC*= AMENDMENTS STANDARD BUILDING CODE
  
 THIS REVIEW WAS COMPLETED USING THE 1997
 STANDARD BUILDING CODE, THE PLANS DO NOT
 INDICATE AS TO WHICH CODE THEY ARE DE-
 SIGNED TOO? PLANS SUBMITTED BETWEEN JAN
 & FEB 2002 MAY BE DESIGNED & SUBMITTED
 UNDER EITHER THE 1997 SBC OR 2001 FL
 CODE.
  
 1) SBC 104.2.2* ADDITIONAL INFORMATION
 SUBMIT A SURVEY LESS THAN A YEAR OLD.
 2) SBC 1804.2.7.2(3) MISSING SOILS
 REPORT AND THE MINIMUM SAFE BEARING
 VALUE.
 3) SBC 1606, MISSING THE DESIGN PARAM-
 ETERS & ASSUMPTIONS,ALSO MISSING INFO
 WIND PRESSURE ON ALL OPENINGS BOTH
 POSSITIVE AND NEGATIVE PRESSURES IN-
 CLUDING END ZONES!
 4) PRODUCT APPROVALS:
 GARAGE DOOR, OVERHEAD, WHICH MODEL #
 DOOR SHALL BE USED FOR 9' & 16' OPENINGS
 GARAGE SWING DOOR, EXTERIOR MISSING
 REPORT. MISING REPORT ON GLASS BLOCK,
 ALSO WHAT WALL THICKNESS IS THE GLASS
 BLOCK GOING TO BE?
 5) SBC 2808 BARBECUES-FACTORY BUILT,
 SHALL BE AN APPROVED TYPE AND SHALL BE
 INSTALLED IN ACCORDANCE WITH THE MANU-
 FACTURES INSTRUCTION.
 6) TRUSS CONNECTION VALUES FOR SIMPSON
 & USP DO NOT CORRESPOND WITH THE CURRENT
 2001 CATALOGS. THE ULT. AVERAGE UPLIFT
 SHALL NOT BE USED AS THIS IS THE AVERAGE
 OF RATE FOR FAILURE. THE 160% UPIFT FOR
 YELLOW PINE SHALL BE USED.
 SIMPON HUM412/ HUCM 412 NOT IN CATOLOG?
 SIMPON HGT-2 18,665 CATALOG @160% 10980
 USP HC-10 1472/1543 CAT 1325/1542
 USP SHA-6 10,560 CATALOG 2 PLY 3745
 CATALOG 3 PLY 5615
 SHA-6T CATALOG 7550
 7) MISSING GRAVITY LOADS ON GIRDERS
 8) SHEET A-8 2 STORY DETAIL QUESTION,
 CONTINEOUS LOAD PATH, THE DETAIL INDI-
 CATES THE TIE DOWN OF THE FLOOR TRUSSES
 USING A USP STRAP. THE SAME DETAIL INDI-
 CATES THE TIE DOWN OF THE BOTTOM OF STUD
 TO PLATE AND ANOTHER STRAP ENVERTED TIE-
 ING THE PLATE TO RIM JOIST? IS THIS TRUE
 LY A 1 1/2 X 24" RIM JOIST? THERE IS NO
 TIE FROM THE RIM JOIST TO BOND BEAM!
 9) SHEET A-8 /A-9 DISCREPANCY SHEET A-8
 TYPICAL SECTION INDICATES A (2) COURSE
 BOND BEAM VS. SHEET A-9 "NOTE" WHERE CON
 CRETE IS OVER CBS WALLS PROVIDE A
 8"X12" FORMED / PORED CONCRETE BEAM W
 4@5'S, MISSING INFORMATION HOOPS OVER
 OPENINGS?
 10) SHEET A-9 STAIR DETAIL: SBC 1007.3.1
 2R+1T=>24" BUT <25".
 11) CONTRACTOR SHALL SUBMIT PLANS TO
 PB COUNTY FOR ASSESSMENT FOR IMPACT FEES
 BUILDING PLAN REVIW
 JIM WITMER
 (561)659-8096X8412