2002-12-02 00:00:00DENIED:
  
 AS PER 2001 FBC 705.6, ALL PENETRATIONS
 OF A FLOOR, FLOOR/CEILING ASSEMBLY, OR
 CEILING MEMBRANE OF A ROOF/CEILING
 ASSEMBLY SHALL BE PROTECTED BY SHAFT
 ENCLOSURE IN ACCORDANCE WITH 705.2 OR
 SHALL COMLY WITH 705.6.1.1 OR 705.6.1.2.
  
 PROVIDE OUTSIDE AIR CACULATIONS FOR THE
 RESIDENTIAL SPACES.SHOW COMPLIANCE
 WITH 2001 FBC(M) 402.2 FOR NATURAL
 VENTILATION OR TABLE 403.3 MECHANICAL
 VENTILATION.
  
 BEDROOM AREAS REQUIRE RETURN AIR -
 BALANCED RETURN AIR - 2001 FBC(M) 601.4
 RETURN AIR SHALL BE EQUAL TO SUPPLY
 AIR BY MEANS OF AIR TRANSFER OR A RETURN
 AIR (JUMPER).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.