| Plan Review Notes For Permit 02022328 |
| Permit Number |
02022328 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-12-02 00:00:00 | DENIED: | | | | | | AS PER 2001 FBC 705.6, ALL PENETRATIONS | | | OF A FLOOR, FLOOR/CEILING ASSEMBLY, OR | | | CEILING MEMBRANE OF A ROOF/CEILING | | | ASSEMBLY SHALL BE PROTECTED BY SHAFT | | | ENCLOSURE IN ACCORDANCE WITH 705.2 OR | | | SHALL COMLY WITH 705.6.1.1 OR 705.6.1.2. | | | | | | PROVIDE OUTSIDE AIR CACULATIONS FOR THE | | | RESIDENTIAL SPACES.SHOW COMPLIANCE | | | WITH 2001 FBC(M) 402.2 FOR NATURAL | | | VENTILATION OR TABLE 403.3 MECHANICAL | | | VENTILATION. | | | | | | BEDROOM AREAS REQUIRE RETURN AIR - | | | BALANCED RETURN AIR - 2001 FBC(M) 601.4 | | | RETURN AIR SHALL BE EQUAL TO SUPPLY | | | AIR BY MEANS OF AIR TRANSFER OR A RETURN | | | AIR (JUMPER). | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|