| Plan Review Notes For Permit 02022325 |
| Permit Number |
02022325 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-05-14 00:00:00 | THE THREE SETS OF PLANS PROVIDED CALL | | | OUT A "SPRAY POLYURETHANE FOAM ROOFING | | | SYSTEM"PROVIDE AN EVALUATION REPORT | | | FROM A RECOGNIZED AGENCY FOR THE FIRE | | | AND WIND RESISTANCE CLASSIFICATION.IF | | | THE ATTACHED REPORT FROM METRO DADE FOR | | | ULTRAGUARD PVC IS INTENDED TO BE USED, | | | PLEASE AMEND THE PLANS TO REFLECT THAT. | | | | | | THE PLANS STILL INDICATE THE USE OF | | | PLYWOOD IN THE EXTERIOR WALL, AS NOTED | | | IN THE 3/8/02 CHECKLIST, PLEASE REVISE | | | AS NECESSARY. | | | | | | PLEASE PROVIDE THE PRODUCT EVALUATION | | | REPORT FOR THE SPECIFIC DRYVIT SYSTEM | | | TO BE USED AS PREVIOUSLY REQUESTED.IF | | | THE PAREX SYSTEM IS TO BE USED, PROVIDE | | | THATEVALUATION REPORT AND AMEND THE | | | PLANS ACCORDINGLY. | | | | | | PROVIDE A SPECIFIC CONNECTION DETAIL FOR | | | THE "SUSPENDED CLOUDS" INCLUDING AN | | | ANALYSIS OF THE EXISTING STRUCTURE TO | | | ACCEPT THE ADDED LOADS. |
|