| 2002-03-04 00:00:00 | | | | PLAN SHEET E-M-201, PLEASE CLARIFY | | | EXISTING A/C RETURN FROM ROOMS A109 | | | THROUGH A111.IS THIS RETURN AIR OR | | | EXHAUST?AS PER 1997 SMC 503.3.1, AIR | | | EXHAUSTED FROM BATH, TOILET, URINAL, | | | LAVATORY, LOCKER, COAT ROOM OR SIMILAR | | | ROOMS SHALL NOT BE RECIRCULATED. | | | | | | INDICATE MANUFACTURER, MODEL, & TONNAGE | | | OF EXISTING RTU. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|