| 2002-03-08 00:00:00 | SHEET A103, PROVIDE TEST REPORTS FOR THE | | | SKYLIGHTS TO BE INSTALLED DEMONSTRATING | | | COMPLIANCE WITH HURRICANE MISSILE | | | IMPACT RESISTANCE. SEE SBC 1707.4 AS | | | AMENDED. | | | | | | PROVIDE TEST REPORTS FOR THE ROOF | | | COVERING FOR WIND AND FIRE.SEE SBC | | | 1503 | | | | | | THE PLANS INDICATE THE PROPOSED USE OF | | | PLYWOOD IN THE EXTERIOR WALLS.THE | | | EXTERIOR WALLS OF BUILDINGS LOCATED IN | | | THE FIRE DISTRICT ARE REQUIRED TO BE OF | | | NON-COMBUSTIBLE CONSTRUCTION.SEE SBC F | | | 102.1 | | | | | | SHEET A202 SHOW THE SERVICE ASVISORS | | | BOOTHS ON AN HC ACCESSIBLE ROUTE. | | | | | | PROVIDE THE EVALUATION REPORT FOR THE | | | DRYVIT SYSTEM TO BE USED. | | | | | | PROVIDE THE HURRICANE MISSILE IMPACT REP | | | ORTS FOR THE GLAZING SYSTEM TO BE USED I | | | N THE SERVICE ADVISORS BOOTHS. | | | | | | WHAT ARE THE "SUSPENDED CLOUDS"? |
|