Text |
| 2002-03-21 00:00:00 | | | | PLEASE CLARIFY THE "RELOCATING" OF | | | EXISTING AHU. | | | | | | PROVIDE RETURN AIR LOCATION.PLEASE | | | NOTE, "LAUNDRY ROOM" CANNOT BE USED AS | | | AN INTERGAL PART TO THE DUCT SYSTEM OR | | | PLENUM.1997 SMC 609.1.1. | | | | | | ARE DUCTS SHOWN ON PLAN ADDITIONAL | | | DUCTWORK TO EXISTING SYSTEM OR | | | REPLACEMENT OF EXISTING DUCTWORK. | | | | | | PROVIDE DUCT SIZE OF MAIN SUPPLY DUCT. | | | | | | SHOULD DUCTWORK SHOWN ON PLAN BE AN | | | ADDITION TO THE EXISTING SYSTEM, | | | PROVIDE MAKE, MODEL & BTUS OF EXISTING | | | AHU. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|