Plan Review Notes
Plan Review Notes For Permit 02022301
Permit Number 02022301
Review Stop M
Sequence Number 1
Notes
Date Text
2002-03-11 00:00:00*******************DENIED***************
  
 INSUFFICIENT INFORMAION FOR MECHANICAL
 REVIEW.PLEASE PROVIDE THE FOLLOWING
 INFORMATION.
  
 1.PROVIDE SIZE OF DUCTWORK BEING
 INSTALLED.
  
 2.INDICATE GRILLE SIZE & CFM
 DISTRIBUTION.
  
 3.PROVIDE BTU INFORMATION FOR THE
 EXISTING GAS WATER HEATER.
  
 4.INDICATE SIZE OF NEW FLUE PIPE.
  
 PLEASE NOTE, ADDTIONAL PERMIT REQUIRED
 FOR GAS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.