Plan Review Notes
Plan Review Notes For Permit 02022301
Permit Number 02022301
Review Stop E
Sequence Number 1
Notes
Date Text
2002-03-06 00:00:00***************** UNSAT ***************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2)NOTE: PLEASE CLARIFY IF THERE IS A
 DOOR GOING INTO MASTER BEDROOM. NONE
 SHOWN ON ELECTRICAL PLAN. PLEASE NOTE
 THAT A SD IS REQ`D INSIDE AND OUTSIDE
 RM.
 PLEASE NOTE SD`S WILL BE REQD IN
 EXISTING BEDROOMS.
  
 3)NOTE: PLEASE NOTE LOAD CALCS SHOW
 WASHER, BUT NONE SHOWN ON PLANS OR PANEL
 SCHEUDLE? PLEASE CLARIFY.
  
 4)NOTE: PLEASE NOTE LOADS FOR A/C`S
 ARE SHOWN AT 5KW AND 8KW AND SHOWN AT
 14500 ON LOAD CALCS, PLEASE CORRELATE.
  
 5)NOTE: PLEASE CLARIFY TWO WATER SPA
 CIRCUITS AND LOADS? ELEC ON E-2 ONLY
 SHOWS ONE?
  
 6)NOTE: PLEASE NOTE MISSING GFI OUTLET
 ON KITCHEN PENINSULAR. 210-52-C-3
  
 7)NOTE: PLEASE CLARIFY DISPOSAL SHOWN
 ON LOAD CALCS, BUT NOT ON PANEL SCHEDULE
 ?
  
 8)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 PROTECTION FOR BEDRROMS, PER 210-12.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372