| 2002-03-06 00:00:00 | ***************** UNSAT *************** |
| | |
| | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110-9. |
| | |
| | 2)NOTE: PLEASE CLARIFY IF THERE IS A |
| | DOOR GOING INTO MASTER BEDROOM. NONE |
| | SHOWN ON ELECTRICAL PLAN. PLEASE NOTE |
| | THAT A SD IS REQ`D INSIDE AND OUTSIDE |
| | RM. |
| | PLEASE NOTE SD`S WILL BE REQD IN |
| | EXISTING BEDROOMS. |
| | |
| | 3)NOTE: PLEASE NOTE LOAD CALCS SHOW |
| | WASHER, BUT NONE SHOWN ON PLANS OR PANEL |
| | SCHEUDLE? PLEASE CLARIFY. |
| | |
| | 4)NOTE: PLEASE NOTE LOADS FOR A/C`S |
| | ARE SHOWN AT 5KW AND 8KW AND SHOWN AT |
| | 14500 ON LOAD CALCS, PLEASE CORRELATE. |
| | |
| | 5)NOTE: PLEASE CLARIFY TWO WATER SPA |
| | CIRCUITS AND LOADS? ELEC ON E-2 ONLY |
| | SHOWS ONE? |
| | |
| | 6)NOTE: PLEASE NOTE MISSING GFI OUTLET |
| | ON KITCHEN PENINSULAR. 210-52-C-3 |
| | |
| | 7)NOTE: PLEASE CLARIFY DISPOSAL SHOWN |
| | ON LOAD CALCS, BUT NOT ON PANEL SCHEDULE |
| | ? |
| | |
| | 8)NOTE: PLEASE LIST THE REQ`D ARC FAULT |
| | PROTECTION FOR BEDRROMS, PER 210-12. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |