Plan Review Notes
Plan Review Notes For Permit 02022301
Permit Number 02022301
Review Stop B
Sequence Number 1
Notes
Date Text
2002-03-15 00:00:00SBC 3401.5 REQUIRES THAT THE ENTIRE
 BUILDING BE BROUGHT UP TO CURRENT CODES
 WHEN A BUILDING IS INCREASED IN HEIGHT.
  
 PROVIDE CALCULATIONS AND PLANS PREPARED
 BY A PROFESSIONAL ENGINEER
 DEMONSTRATING THE EXISTING BUILDING
 WILL SUPPORT ALL OF THE STRUCTURAL
 LOADS THAT WILL BE IMPOSED UPON IT BY
 THE ADDITION. SEE SBC 104.2.
  
 SHEET S2 SHOWS A PORTION OF THE
 PROPOSED SECOND FLOOR TO BE PLACED ON
 THE TOP CHORD OF THE EXISTING TRUSSES
 WITHOUT ADDITIONAL SUPPORT.THIS IS
 NOT A VIABLE DESIGN.
  
 THE AREA OF THE OPENINGS ON THE WEST
 ELEVATION OF THE ADDITION EXCEED THE
 20% ALLOWED BY SBC TABLE 600 FOR TYPE
 VI CONSTRUCTION LOCATED 3' TO 10' FROM A
 PROPERTY LINE.PLEASE REVISE AS
 NECESSARY.
  
  
 THE ADDITION WILL BE SUBJECT TO IMPACT
 FEES COLLECTED BY THE COUNTY FOR THE
 CITY.THE PERMIT PLANS MUST BE STAMPED
 BY THAT OFFICE AND A COPY OF THE PAID
 RECEIPT ATTACHED TO THE PERMIT
 APPLICATION.CALL 233-5025 FOR MORE
 INFORMATION.