| Plan Review Notes For Permit 02022300 |
| Permit Number |
02022300 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2002-12-27 00:00:00 | *********** UNSAT ****************** | | | | | | 1)NOTE: PLEASE CORRELATE LOAD CALCULAT- | | | IONS. PLEASE CLARIFY HOW LOADS CAN BE | | | THE SAME ON ALL PANELS, WHEN SOME HAVE | | | MORE ITEMS/LOADS SHOWN ON PANEL SCHEDULE | | | ?? | | | | | | 2)NOTE: PLEASE NOTE PLANS/RISER STILL | | | DO NOT SHOW ANY MAINS. 225-31/ PLEASE | | | NOTE MAINS ARE TO BE GROUPED PER SERVICE | | | 230-72. | | | | | | 3)NOTE: PLEASE NOTE EQUIPMENT GROUNDING | | | CONDUCTORS ARE STILL MISSING FROM MAINS | | | TO PANELS??? THIS IS THE THIRD TIME | | | IT HAS BEEN NOTED AND/OR COMMENTED ON. | | | PLEASE SEE LETTER ATTACHED PER FS/FAC | | | W/ RESPECT TO DESIGN PROFESSIONAL. | | | 553.80(2) (B). | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 | | | EXT 8372 |
|