Plan Review Notes
Plan Review Notes For Permit 02022300
Permit Number 02022300
Review Stop P
Sequence Number 1
Notes
Date Text
2002-04-01 00:00:00DENIED
 REFERENCE: SPC-94 - FHA AMEND-98 DESIGN
 MANUAL
  
 1) SHT A-16 SANITARY RISER DIAGRAM UNITS
 "A" & "C" - BATH #3 FROM "C" UNIT SHALL
 NOT DRAIN PAST LAUNDRY TRAY ON FIRST
 FLOOR. BATH #3 SHALL BE TAKEN OFF BELOW
 LAUNDRY TRAY.
 2) SHT A-16 SANITARY RISER DIAGRAM UNITS
 "A" & "C" - MASTER BATH FROM "C" UNIT
 SHALL NOT DRAIN INTO 2" DRAIN FROM SHOW-
 ER. RISER FOR MASTER BATH SHALL BE TAKEN
 OFF BEFORE MASTER BATH IN "A" UNIT.
 3) SHT A-16 SANITARY RISER DIAGRAM UNITS
 "B" & "D" - LAUNDRY TRAY NOT SHOWN FOR
 UNIT "D"
 4) SHT 1-16 SANITARY RISER DIAGRAM UNITS
 "B" & "D" - MASTER BATH FROM "D" UNIT
 SHALL NOT DRAIN INTO 2" DRAIN FROM SHOW-
 ER. RISER FOR MASTER BATH SHALL BE TAKEN
 OFF BEFORE MASTER BATH IN "B" UNIT.
  
 REVIEW BY KEN STEVENS