| Plan Review Notes For Permit 02022300 |
| Permit Number |
02022300 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-03-20 00:00:00 | ****************** UNSAT ************** | | | | | | 1)NOTE: PLEASE NOTE THAT RISER DIAGRAM | | | SHOWS MAIN? DISCONNECT BETWEEN METERS | | | AND PANELS? PLEASE SHOW LOCATION OF | | | THESE DISC`S ON PLANS. | | | PLEASE NOTE THAT 150A PANELS HAVE NO | | | INDICATIONS IF THEY ARE "MLO" OR "MCB"?? | | | | | | 2)NOTE: PLEASE NOTE, IF A MAIN IS USED | | | BETWEEN METER AND PANEL, THEN AND | | | EQUIPMENT GROUNDING CONDUCTOR IS REQ`D | | | BETWEEN MAIN DISC AND PANEL. SIZE PER | | | 250-122. | | | | | | 3)NOTE: PLEASE NOTE MISSING SD`S AT THE | | | BOTTOM OF STAIRS AT ENTRANCE FOR UPPER | | | UNITS. NFPA-72, 2-2.1.1.1/2-5.2.1.3. | | | | | | 4)NOTE: PLEASE LIST THE REQ`D ARC FAULT | | | PROTECTED CIRCUITS ON PANEL SCHEDULE | | | PER 210-12. | | | | | | 5)NOTE: PLEASE SEE OPT PAGE A-18, | | | PLEASE NOTE MISSING SD`S. | | | SMOKE DETECTORS ARE REQUIRED | | | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. | | | ALSO ON EACH LEVEL OF A MULTI-LEVEL | | | DWELLING UNIT. ROOMS WITH BATHS AND OR | | | CLOSETS ARE CONSIDERED SLEEPING ROOMS. | | | PER NFPA-72 2-2.1.1.1. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|