Plan Review Notes
Plan Review Notes For Permit 02022300
Permit Number 02022300
Review Stop E
Sequence Number 1
Notes
Date Text
2002-03-20 00:00:00****************** UNSAT **************
  
 1)NOTE: PLEASE NOTE THAT RISER DIAGRAM
 SHOWS MAIN? DISCONNECT BETWEEN METERS
 AND PANELS? PLEASE SHOW LOCATION OF
 THESE DISC`S ON PLANS.
 PLEASE NOTE THAT 150A PANELS HAVE NO
 INDICATIONS IF THEY ARE "MLO" OR "MCB"??
  
 2)NOTE: PLEASE NOTE, IF A MAIN IS USED
 BETWEEN METER AND PANEL, THEN AND
 EQUIPMENT GROUNDING CONDUCTOR IS REQ`D
 BETWEEN MAIN DISC AND PANEL. SIZE PER
 250-122.
  
 3)NOTE: PLEASE NOTE MISSING SD`S AT THE
 BOTTOM OF STAIRS AT ENTRANCE FOR UPPER
 UNITS. NFPA-72, 2-2.1.1.1/2-5.2.1.3.
  
 4)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 PROTECTED CIRCUITS ON PANEL SCHEDULE
 PER 210-12.
  
 5)NOTE: PLEASE SEE OPT PAGE A-18,
 PLEASE NOTE MISSING SD`S.
 SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372