Plan Review Notes
Plan Review Notes For Permit 02022300
Permit Number 02022300
Review Stop B
Sequence Number 1
Notes
Date Text
2002-04-08 00:00:00SHEET A1 IS MISSING THE FOOTING
 DESIGNATIONS.PLEASE REVISE AS
 NECESSARY.
  
 DETAIL 27/A11 IS NOT CLEAR AS TO HOW THE
 VAULTED CEILING TRUSSES WILL
 TRANSITIONTO THE WOOD FRAME WALL FOR
 BRACING.
  
 THE RISE RUN RATIO FOR STAIRS IS
 MEASURED EXCLUSIVE OF NOSING.SEE SBC
 1007.3.1 IT APPEARS THE SECTION ON
 SHEET A7 INCORPORATES THE NOSING.
  
 SHEET A13 THE DIAPHRAGM SCHEDULE NOTES
 THE WALL FRAMING @ 16" OC AND SHEET A 7
 CALLS OUT 24" SPACING.PLEASE REVISE
 AS NECESSARY.
  
 SECTION 8/A8 CALLS OUT A SOFFIT VENT 4 X
 24 SPACED 8' ON CENTER.PROVIDE AN
 ATTIC AREA CALCULATION AND INCLUDE THE
 FREE AREA OF THE SOFFIT VENT SCREEN.
 ALSO, PLEASE SPECIFY THE "CEMENTITOUS"
 SOFFIT MATERIAL.
  
 BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY FOR THE CITY, THE
 PERMIT PLANS STAMPED BY THAT OFFICE AND
 A COPY OF THE PAID RECEIPT ATTACHED TO
 THE PERMIT APPLICATION.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved