Plan Review Notes
Plan Review Notes For Permit 02022293
Permit Number 02022293
Review Stop E
Sequence Number 3
Notes
Date Text
2002-08-13 00:00:00************** UNSAT *****************
  
 PLEASE SEE NOTE ATTACHED FOR FS/FAC.
 PLEASE NOTE THAT PLANS BEING TURNED
 DOWN FOR THE SAME COMMENTS FOUR OR MORE
 TIMES ARE SUBJECT TO 4X FEE FOR PLAN
 REVIEW PORTION OF FEES.
  
 1)NOTE: PLEASE NOTE THAT ELECTRICAL
 RISER DIAGRAM IS STILL NOT SHOWING ANY
 MAINS? PLEASE NOTE PANELS SHOWN AS "MLO"
 PLEASE ALSO NOTE THAT NO MAINS ARE
 SHOWN ON PLANS. A-14.
  
  
 2)NOTE; PLEASE NOTE THAT AN EQUIPMENT
 GRND IS REQ`D BETWEEN MAINS AND PANELS.
 250-122
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PLAMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372