| 2002-07-23 00:00:00 | BUILDING DENIED |
| | |
| | 1) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 2) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 3) THE ATTIC VENTING CALCULATIONS ARE |
| | NOT CORRECT. THE 6240 SQ.FT. OF ATTIC |
| | WHEN DIVIDED BY 150 SQ.FT. REQUIRES |
| | 41.6 SQ.FT. OF NET FREE VENTILATING AREA |
| | DETERMINE THE NET FREE VENT AREA OF THE |
| | 4"X24" SCEEN VENT (MANUFACTURERS SPECS.) |
| | AND INDICATE THE NUMBER OF SCREEN VENTS |
| | THAT WILL BE REQUIRED. THE CALCULATIONS |
| | FOR 1ST FLOOR ATTIC SPACE IS ALSO |
| | INCORRECT. |
| | |
| | 4) SUBMIT A WRITTEN PLAN TO THE BUILDING |
| | OFFICIAL FOR HURRICANE MISSLE IMPACT FOR |
| | HIS APPROVAL. |
| | THE PLAN MUST INCLUDE THE FOLLOWING |
| | INFORMATION: |
| | A) WHO WILL INSTALL PANELS (MUST BE |
| | BUILDING STAFF) |
| | B) ESTIMATED TIME TO INSTALL |
| | C) INDICATE ON PLANS WHERE THEY WILL BE |
| | STORED ON SITE (IF STORED IN STANDING |
| | POSITION, AN ENGINEER IS TO DESIGN THE |
| | ENCLOSURE) |
| | D) PANELS ON FIRST FLOOR ONLY, WITHOUT |
| | USE OF LADDERS OR LIFTS |
| | E) BUILDING OFFICIAL MUST APPROVE THE |
| | WRITTEN PLAN |
| | |
| | 5) ENGINEERED TRUSS DRAWINGS AND LAYOUT |
| | WILL BE REQUIRED TO BE SUBMITTED FOR |
| | REVIEW PRIOR TO INSTALLATION. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)659-8096 EXT.8202 |