| Plan Review Notes For Permit 02022293 |
| Permit Number |
02022293 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-03-09 00:00:00 | DENIED; | | | 1.PAGE A-16 PLUMBING RISER UNITS A & C. | | | A.SECOND FLOOR MASTER BATH 3" RISER | | | CANNOT DISCHARGE INTO 2" SHOWER | | | DRAIN. | | | B.W/C WET VENT. PIPE SIZE MUST | | | INCREASE FROM 2" TO 3" WHEN THE | | | FIXTURE LOAD IS MORE THAN 4 FU'S. | | | 2.PAGE A-16 PLUMBING RISER UNITS B & D. | | | A. SEE NOTE 1-A & B. | | | B.LAUNDRY TUB MISSING FOR UNIT D. | | | 3.SHOW DIMENSIONS FOR MASTER BATH W/C | | | TO COMPLY WITH FHA 7.43. MOST CONST- | | | UCTION COMPANY'S DO NOT HAVE THE FHA | | | DESIGN MANUAL. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT 8369 |
|