| 2002-03-22 00:00:00 | ***************** UNSAT ************* |
| | |
| | 1)NOTE: PLEASE NOTE THAT RISER DIAGRAM |
| | SHOWS MAIN DISCONNECTS BETWEEN METERS |
| | AND PANELS. PLEASE SHOW LOCATION OF |
| | THESE DISC`SON PLANS. |
| | PLEASE NOTE THAT 150A PANELS HAVE NO |
| | INDICATION OF BEING "MCB" OR "MLO" |
| | |
| | 2)NOTE: PLEASE NOTE THAT IF A MAIN |
| | DISCONNECT IS USED, THEN AN EQUIPMENT |
| | GROUNDING CONDUCTOR MAY IS REQ`D. SIZE |
| | PER 250-122. |
| | |
| | 3)NOTE: PLEASE NOTE MISSING SD`S AT THE |
| | BOTTOM OF STAIRS FOR UPPER UNITS. PLEASE |
| | SEE NFPA-72 2-2.1.1.1/ 2-5.2.1.3. |
| | |
| | 4)NOTE: PLEASE LIST THE REQUIRED ARC |
| | FAULT PROTECTED CIRCUITS ON PANEL |
| | SCHEDULE PER 210-12. |
| | |
| | 5)NOTE: PLEASE NOTE MISSING SD`S FOR |
| | ROOMS THAT ARE ADAPTABLE SLEEPING ROOMS |
| | WITH CLOSETS AND/OR BATHS. NFPA-72 |
| | 2-2.1.1.1. UPPER UNIT/DEN. |
| | |
| | 6)NOTE: PLEASE SEE OPT PAGE A-18, PLEASE |
| | NOTE MISSING MANY SD`S. INSIDE AND OUT- |
| | -SIDE ALL SLEEPING ROOMS AND ON EACH |
| | LEVEL OF MULTI LEVEL UNITS. SD`S ARE TO |
| | BE CLOSE VICINTY OF STAIRS ON EACH LEVEL |
| | . |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | ' |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |