Plan Review Notes
Plan Review Notes For Permit 02022293
Permit Number 02022293
Review Stop E
Sequence Number 1
Notes
Date Text
2002-03-22 00:00:00***************** UNSAT *************
  
 1)NOTE: PLEASE NOTE THAT RISER DIAGRAM
 SHOWS MAIN DISCONNECTS BETWEEN METERS
 AND PANELS. PLEASE SHOW LOCATION OF
 THESE DISC`SON PLANS.
 PLEASE NOTE THAT 150A PANELS HAVE NO
 INDICATION OF BEING "MCB" OR "MLO"
  
 2)NOTE: PLEASE NOTE THAT IF A MAIN
 DISCONNECT IS USED, THEN AN EQUIPMENT
 GROUNDING CONDUCTOR MAY IS REQ`D. SIZE
 PER 250-122.
  
 3)NOTE: PLEASE NOTE MISSING SD`S AT THE
 BOTTOM OF STAIRS FOR UPPER UNITS. PLEASE
 SEE NFPA-72 2-2.1.1.1/ 2-5.2.1.3.
  
 4)NOTE: PLEASE LIST THE REQUIRED ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE PER 210-12.
  
 5)NOTE: PLEASE NOTE MISSING SD`S FOR
 ROOMS THAT ARE ADAPTABLE SLEEPING ROOMS
 WITH CLOSETS AND/OR BATHS. NFPA-72
 2-2.1.1.1. UPPER UNIT/DEN.
  
 6)NOTE: PLEASE SEE OPT PAGE A-18, PLEASE
 NOTE MISSING MANY SD`S. INSIDE AND OUT-
 -SIDE ALL SLEEPING ROOMS AND ON EACH
 LEVEL OF MULTI LEVEL UNITS. SD`S ARE TO
 BE CLOSE VICINTY OF STAIRS ON EACH LEVEL
 .
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
 '
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372