| 2002-04-12 00:00:00 | *************BUILDING DENIED************ |
| | |
| | 1) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 2) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 3) PROVIDE A KEY PLAN AND INSTALLATION |
| | SCHEDULE FOR THE STORM PANELS OR APPLY |
| | UNDER A SEPARATE PERMIT. REMOVABLE STORM |
| | PANELS CAN NOT BE USED ABOVE THE GROUND |
| | FLOOR. IMPACT RESISTANT GLAZING OR |
| | PERMANETLY AFFIXED PROTECTIVE DEVICES SH |
| | ALL BE INSTALLED. PERMANENTLY AFFIXED |
| | PROTECTIVE DEVICES REQUIRE THE WRITTEN |
| | APPROVAL OF THE BUILDING OFFICIAL. |
| | |
| | 4) SHEET A1 IS MISSING THE FOOTING |
| | DESIGNATIONS. PLEASE CORRECT. |
| | |
| | 5) PLEASE CLARIFY DETAIL 27/A11 AS TO |
| | HOW GABLE END WILL BE CONSTRUCTED AT THE |
| | VAULTED CEILING AT SECOND FLOOR BEDROOM. |
| | |
| | 6) THE BALCONY RAIL IS SHOWN ON SHEET A5 |
| | WITH A 4" SPACE BELOW THE BOTTOM RAIL. |
| | THIS WILL NOT REJECT A 2" SPHERE AS CODE |
| | REQUIRES. PLEASE CORRECT. |
| | |
| | 7) THE FRONT ELEVATION ON A5 INDICATES A |
| | CEMENTITIOUS FINISH OVER CONCRETE BLOCK |
| | AT THE SECOND FLOOR BEDROOM, WHICH IS |
| | WOOD FRAME. PLEASE CORRECT. |
| | |
| | 8) THE FIRE RATED DOORS BETWEEN THE |
| | UNITS AND THE GARAGE ARE REQUIRED TO |
| | HAVE APPROVED CLOSERS PER 97SBC SECT. |
| | 705.1.3.5. |
| | |
| | 9) THE RISE AND RUN DIMENSIONS ON DETAIL |
| | 1/A7 DO NOT CORRESPOND WITH THOSE GIVEN |
| | IN SECTION B-B. TREADS EXCLUSIVE OF |
| | NOSING IS REQUIRED TO BE A MINIMUM OF 9" |
| | WIDE AND TREADS LESS THAN 10" WIDE ARE |
| | REQUIRED TO HAVE A NOSING OF APPROX. 1". |
| | 97SBC SECT. 1007.3.2 & 1007.3.3 SECTION |
| | B-B INDICATES A 9.5" WIDE TREAD |
| | INCLUDING THE NOSING. PLEASE CORRECT. |
| | |
| | 10) THE DIAPHRAM SCHEDULE ON A13 NOTES |
| | 16"O.C. WALL FRAMING AND A7 INDICATES |
| | 24" SPACING. PLEASE CORRECT. |
| | |
| | 11) SECTION 8/A8 CALLS FOR 4"X24" SOFFIT |
| | VENTS SPACED 8'O.C. PROVIDE AN ATTIC |
| | AREA CALCULATION AND INCLUDE THE FREE |
| | AREA OF THE SOFFIT VENT SCREEN. ALSO, |
| | PLEASE SPECIFY THE "CEMENTITIOUS" |
| | SOFFIT MATERIAL. |
| | |
| | 12) PROVIDE WINDOW, DOOR AND GARAGE DOOR |
| | BUCK FASTENING DETAILS. |
| | |
| | 13)DETAILS 13 & 23 ON A11 ARE MISLABELED |
| | AS A17. PLEASE CORRECT. |
| | |
| | 14) DETAIL 23 ON A11 MUST INDICATE THAT |
| | THE ONE HOUR TENANT SEPARATION IS |
| | MAINTAINED TO THE UNDERSIDE OF THE ROOF |
| | SHEATHING. |
| | |
| | 15) PROVIDE AN ADDITIONAL COPY OF THE |
| | PRODUCT APPROVAL FOR THE FRONT DOOR. |
| | (TWO ARE REQUIRED) |
| | |
| | 16) THE OPTIONS SHOWN ON SHEETS A17-A19 |
| | MUST COMPLY WITH THE REQUIREMENTS OF THE |
| | FAIR HOUSING ACT. |
| | |
| | 17) THE PA23 CONNECTOR LISTED IN DETAIL |
| | 19 ON A11 FOR TRUSS GT2, IS A PURLIN |
| | ANCHOR AND IS NOT DESIGNED FOR USE AS A |
| | TRUSS ANCHOR. |
| | |
| | 18) PLEASE SPECIFY A CONNECTOR OR |
| | CONNECTION DETAIL FOR TRUSS GT1. DETAIL |
| | 32 ON A11 INDICATES THE ATTACHMENT OF |
| | THE WOOD FRAME WALL TO THE MASONRY. |
| | |
| | 19) NO TRUSS DRAWINGS WERE SUBMITTED |
| | WITH THE TRUSS LAYOUTS. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)659-8096 EXT.8202 |