Plan Review Notes
Plan Review Notes For Permit 02022293
Permit Number 02022293
Review Stop B
Sequence Number 1
Notes
Date Text
2002-04-12 00:00:00*************BUILDING DENIED************
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) PROVIDE A KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS OR APPLY
 UNDER A SEPARATE PERMIT. REMOVABLE STORM
 PANELS CAN NOT BE USED ABOVE THE GROUND
 FLOOR. IMPACT RESISTANT GLAZING OR
 PERMANETLY AFFIXED PROTECTIVE DEVICES SH
 ALL BE INSTALLED. PERMANENTLY AFFIXED
 PROTECTIVE DEVICES REQUIRE THE WRITTEN
 APPROVAL OF THE BUILDING OFFICIAL.
  
 4) SHEET A1 IS MISSING THE FOOTING
 DESIGNATIONS. PLEASE CORRECT.
  
 5) PLEASE CLARIFY DETAIL 27/A11 AS TO
 HOW GABLE END WILL BE CONSTRUCTED AT THE
 VAULTED CEILING AT SECOND FLOOR BEDROOM.
  
 6) THE BALCONY RAIL IS SHOWN ON SHEET A5
 WITH A 4" SPACE BELOW THE BOTTOM RAIL.
 THIS WILL NOT REJECT A 2" SPHERE AS CODE
 REQUIRES. PLEASE CORRECT.
  
 7) THE FRONT ELEVATION ON A5 INDICATES A
 CEMENTITIOUS FINISH OVER CONCRETE BLOCK
 AT THE SECOND FLOOR BEDROOM, WHICH IS
 WOOD FRAME. PLEASE CORRECT.
  
 8) THE FIRE RATED DOORS BETWEEN THE
 UNITS AND THE GARAGE ARE REQUIRED TO
 HAVE APPROVED CLOSERS PER 97SBC SECT.
 705.1.3.5.
  
 9) THE RISE AND RUN DIMENSIONS ON DETAIL
 1/A7 DO NOT CORRESPOND WITH THOSE GIVEN
 IN SECTION B-B. TREADS EXCLUSIVE OF
 NOSING IS REQUIRED TO BE A MINIMUM OF 9"
 WIDE AND TREADS LESS THAN 10" WIDE ARE
 REQUIRED TO HAVE A NOSING OF APPROX. 1".
 97SBC SECT. 1007.3.2 & 1007.3.3 SECTION
 B-B INDICATES A 9.5" WIDE TREAD
 INCLUDING THE NOSING. PLEASE CORRECT.
  
 10) THE DIAPHRAM SCHEDULE ON A13 NOTES
 16"O.C. WALL FRAMING AND A7 INDICATES
 24" SPACING. PLEASE CORRECT.
  
 11) SECTION 8/A8 CALLS FOR 4"X24" SOFFIT
 VENTS SPACED 8'O.C. PROVIDE AN ATTIC
 AREA CALCULATION AND INCLUDE THE FREE
 AREA OF THE SOFFIT VENT SCREEN. ALSO,
 PLEASE SPECIFY THE "CEMENTITIOUS"
 SOFFIT MATERIAL.
  
 12) PROVIDE WINDOW, DOOR AND GARAGE DOOR
 BUCK FASTENING DETAILS.
  
 13)DETAILS 13 & 23 ON A11 ARE MISLABELED
 AS A17. PLEASE CORRECT.
  
 14) DETAIL 23 ON A11 MUST INDICATE THAT
 THE ONE HOUR TENANT SEPARATION IS
 MAINTAINED TO THE UNDERSIDE OF THE ROOF
 SHEATHING.
  
 15) PROVIDE AN ADDITIONAL COPY OF THE
 PRODUCT APPROVAL FOR THE FRONT DOOR.
 (TWO ARE REQUIRED)
  
 16) THE OPTIONS SHOWN ON SHEETS A17-A19
 MUST COMPLY WITH THE REQUIREMENTS OF THE
 FAIR HOUSING ACT.
  
 17) THE PA23 CONNECTOR LISTED IN DETAIL
 19 ON A11 FOR TRUSS GT2, IS A PURLIN
 ANCHOR AND IS NOT DESIGNED FOR USE AS A
 TRUSS ANCHOR.
  
 18) PLEASE SPECIFY A CONNECTOR OR
 CONNECTION DETAIL FOR TRUSS GT1. DETAIL
 32 ON A11 INDICATES THE ATTACHMENT OF
 THE WOOD FRAME WALL TO THE MASONRY.
  
 19) NO TRUSS DRAWINGS WERE SUBMITTED
 WITH THE TRUSS LAYOUTS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202