Plan Review Notes
Plan Review Notes For Permit 02022292
Permit Number 02022292
Review Stop B
Sequence Number 2
Notes
Date Text
2002-07-18 00:00:00SHEETS A9 AND A10.ARCHITECT
 CLARIFY HOW THE ATTIC VENT CALCULATIONS
 WERE ARRIVED AT.AN ATTIC AREA OF 6240
 SQUARE FEET VENTILATED AT THE RATIO OF
 ONE SQUARE FOOT TO EACH 150 SQUARE FEET
 WILL REQUIRE 41.6 SQUARE FEET "NET FREE
 AREA", NOT THE TWENTY FIVE SQUARE FEET
 DECLARED.
  
 THE 4" X 24" SCREENED VENTS WILL LOSE
 AREA TO THE SPACE OCCUPIED BY THE
 SCREENING SOMEWHERE ON THE ORDER OF 40%
 TO 60%. THE NET FREE AREA OPENING OF
 THE VENT IS GENERALLY AVAILABLE FROM
 THE MANUFACTURER OF THE PRODUCT.
  
 THE PREVIOUSLY REQUESTED INFORMATION
 FOR"CEMENTITIOUS" SOFFIT MATERIAL HAS
 NOT
 BEEN PROVIDED.IT IS SOMEWHAT VAGUE
 AND LEAVES A GREAT DEAL TO THE
 IMAGINATION AS TO WHAT MAY APPEAR IN
 THE FINISHED PRODUCT.
  
 PLEASE BE A LITTLE MORE SPECIFIC, IE
 STUCCO OVER LATH, HARDIPANEL, DUROC,
 ETC.
  
 THE USE OF SHUTTERS ON MULTI STORY
 AND/OR MULTIPLE BUILDINGS IN A PROJECT
 ARE SUBJECT TO A SPECIAL EXCEPTION BY
 THE BUILDING OFFICIAL.
  
 THE INFORMATION IN THE METRO DADE NOA
 000602.04, BERTHA SHUTTERS, IS
 ILLEGIBLE.PLEASE PROVIDE CLEAR
 COPIES, IF APPROVED FOR FINAL USE AS
 NOTED ABOVE.
  
 NOA 011120.01 LAWSON MULLION HAS AN
 ILLEGIBLE DRAWING, PLEASE PROVIDE CLEAR
 COPIES.
  
 THE NOA 990803.05 PIONEER ROOF TILE IS
 EXPIRED.
  
 SBCCI REPORT 9606C CLOPAY GARAGE DOORS
 IS ILLEGIBLE.PLEASE PROVIDE CLEAR
 COPIES.
  
 RAMMS ENGINEERING RAILINGS.PLEASE
 PROVIDE COMPLETE CALCULATIONS,
 INCLUDING THE SOURCES USED FOR DESIGN
 IN THE "RATIONAL ANALYSIS" DECLARED.
 DEMONSTRATE COMPLIANCE WITH THE LOADS
 IN FBC 1608.2.2
  
 HOW WILL THE FOUR INCH PICKET SPACING
 DEPICTED IN THE "DECORATIVE OPTION" BE
 ACCOMPLISHED WITH FOUR 3/4" PICKETS?
  
 SPECIFY WHAT THE ANCHORS ARE SHOWN AS
 1/4" X 2 1/2" AND 1/4" X 3".INCLUDE IN
 CALCULATIONS THE LOAD VALUES ASSUMED.
  
 THIS PROJECT WILL REQUIRE A RESIDENT
 INSPECTOR, TO THAT END PLEASE PROVIDE
 PERMIT APPLICATION IN TRIPLICATE.
  
 BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO THE
 COUNTY, THE PERMIT PLANS STAMPED BY
 RECEIPT ATTACHED TO THE PERMIT
 APPLICATION.CALL 561-233-5025 FOR
 MORE INFORMATION.