| 2002-07-18 00:00:00 | SHEETS A9 AND A10.ARCHITECT |
| | CLARIFY HOW THE ATTIC VENT CALCULATIONS |
| | WERE ARRIVED AT.AN ATTIC AREA OF 6240 |
| | SQUARE FEET VENTILATED AT THE RATIO OF |
| | ONE SQUARE FOOT TO EACH 150 SQUARE FEET |
| | WILL REQUIRE 41.6 SQUARE FEET "NET FREE |
| | AREA", NOT THE TWENTY FIVE SQUARE FEET |
| | DECLARED. |
| | |
| | THE 4" X 24" SCREENED VENTS WILL LOSE |
| | AREA TO THE SPACE OCCUPIED BY THE |
| | SCREENING SOMEWHERE ON THE ORDER OF 40% |
| | TO 60%. THE NET FREE AREA OPENING OF |
| | THE VENT IS GENERALLY AVAILABLE FROM |
| | THE MANUFACTURER OF THE PRODUCT. |
| | |
| | THE PREVIOUSLY REQUESTED INFORMATION |
| | FOR"CEMENTITIOUS" SOFFIT MATERIAL HAS |
| | NOT |
| | BEEN PROVIDED.IT IS SOMEWHAT VAGUE |
| | AND LEAVES A GREAT DEAL TO THE |
| | IMAGINATION AS TO WHAT MAY APPEAR IN |
| | THE FINISHED PRODUCT. |
| | |
| | PLEASE BE A LITTLE MORE SPECIFIC, IE |
| | STUCCO OVER LATH, HARDIPANEL, DUROC, |
| | ETC. |
| | |
| | THE USE OF SHUTTERS ON MULTI STORY |
| | AND/OR MULTIPLE BUILDINGS IN A PROJECT |
| | ARE SUBJECT TO A SPECIAL EXCEPTION BY |
| | THE BUILDING OFFICIAL. |
| | |
| | THE INFORMATION IN THE METRO DADE NOA |
| | 000602.04, BERTHA SHUTTERS, IS |
| | ILLEGIBLE.PLEASE PROVIDE CLEAR |
| | COPIES, IF APPROVED FOR FINAL USE AS |
| | NOTED ABOVE. |
| | |
| | NOA 011120.01 LAWSON MULLION HAS AN |
| | ILLEGIBLE DRAWING, PLEASE PROVIDE CLEAR |
| | COPIES. |
| | |
| | THE NOA 990803.05 PIONEER ROOF TILE IS |
| | EXPIRED. |
| | |
| | SBCCI REPORT 9606C CLOPAY GARAGE DOORS |
| | IS ILLEGIBLE.PLEASE PROVIDE CLEAR |
| | COPIES. |
| | |
| | RAMMS ENGINEERING RAILINGS.PLEASE |
| | PROVIDE COMPLETE CALCULATIONS, |
| | INCLUDING THE SOURCES USED FOR DESIGN |
| | IN THE "RATIONAL ANALYSIS" DECLARED. |
| | DEMONSTRATE COMPLIANCE WITH THE LOADS |
| | IN FBC 1608.2.2 |
| | |
| | HOW WILL THE FOUR INCH PICKET SPACING |
| | DEPICTED IN THE "DECORATIVE OPTION" BE |
| | ACCOMPLISHED WITH FOUR 3/4" PICKETS? |
| | |
| | SPECIFY WHAT THE ANCHORS ARE SHOWN AS |
| | 1/4" X 2 1/2" AND 1/4" X 3".INCLUDE IN |
| | CALCULATIONS THE LOAD VALUES ASSUMED. |
| | |
| | THIS PROJECT WILL REQUIRE A RESIDENT |
| | INSPECTOR, TO THAT END PLEASE PROVIDE |
| | PERMIT APPLICATION IN TRIPLICATE. |
| | |
| | BEFORE A PERMIT TO CONSTRUCT MAY BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO THE |
| | COUNTY, THE PERMIT PLANS STAMPED BY |
| | RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION.CALL 561-233-5025 FOR |
| | MORE INFORMATION. |