| 2002-03-20 00:00:00 | ****************** UNSAT ************* | | | | | | 1)NOTE: PLEASE NOTE THAT IRSER DIAGRAM | | | SHOWS MAIN DISCONNECTS BETWEEN METERS | | | AND PANELS? PLEASE SHOW LOCATIONS OF | | | THESE DISC`S ON PLANS.230-72. | | | PLEASE NOTE THAT THERE IS NO INDICATION | | | OF PANELS BEING "MLO" OR "MCB".? | | | | | | 2)NOTE: PLEASE NOTE IF MAIN DISC`S ARE | | | INSTALLED, THEN AN EQUIPMENT GROUNDING | | | CONDUCTOR IS REQ`D BETWEEN MAIN DISC AND | | | PANEL. SIZE PER 250-122. | | | | | | 3)NOTE: PLEASE NOTE MISSING SD`S AT THE | | | BOTTOM OF STAIRS FOR UPPER UNITS,PER | | | NFPA-72 2-2.1.1.1,2-5.2.1.3 | | | | | | 4)NOTE: PLEASE LIST THE REQ`D ACR FAULT | | | PROTECTED CIRCUITS ON PANEL SCHEDULES | | | PER 210-12. | | | | | | 5)NOTE: PLEASE SEE OPT PAGE A-18. PLEASE | | | NOTE MISSING MANY SD`S. | | | SMOKE DETECTORS ARE REQUIRED | | | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. | | | ALSO ON EACH LEVEL OF A MULTI-LEVEL | | | DWELLING UNIT. ROOMS WITH BATHS AND OR | | | CLOSETS ARE CONSIDERED SLEEPING ROOMS. | | | PER NFPA-72 2-2.1.1.1. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|