Plan Review Notes
Plan Review Notes For Permit 02022292
Permit Number 02022292
Review Stop E
Sequence Number 1
Notes
Date Text
2002-03-20 00:00:00****************** UNSAT *************
  
 1)NOTE: PLEASE NOTE THAT IRSER DIAGRAM
 SHOWS MAIN DISCONNECTS BETWEEN METERS
 AND PANELS? PLEASE SHOW LOCATIONS OF
 THESE DISC`S ON PLANS.230-72.
 PLEASE NOTE THAT THERE IS NO INDICATION
 OF PANELS BEING "MLO" OR "MCB".?
  
 2)NOTE: PLEASE NOTE IF MAIN DISC`S ARE
 INSTALLED, THEN AN EQUIPMENT GROUNDING
 CONDUCTOR IS REQ`D BETWEEN MAIN DISC AND
 PANEL. SIZE PER 250-122.
  
 3)NOTE: PLEASE NOTE MISSING SD`S AT THE
 BOTTOM OF STAIRS FOR UPPER UNITS,PER
 NFPA-72 2-2.1.1.1,2-5.2.1.3
  
 4)NOTE: PLEASE LIST THE REQ`D ACR FAULT
 PROTECTED CIRCUITS ON PANEL SCHEDULES
 PER 210-12.
  
 5)NOTE: PLEASE SEE OPT PAGE A-18. PLEASE
 NOTE MISSING MANY SD`S.
 SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372