| 2002-04-01 00:00:00 | DENIED |
| | REFERENCE: SPC-94 - FACBC-97 - SGC-97 |
| | |
| | 1) PLEASE ROUTE PLANS PALM BEACH COUNTY |
| | HEALTH UNIT DIVISION OF ENVIRONMENTAL |
| | HEALTH 901 EVERNIA STREET FOR PLAN RE- |
| | VIEW PRIOR TO RESUBMITTING. |
| | 2) PROVIDE CALCULATIONS FOR MINIMUM FAC- |
| | ILITIES PER TABLE 407 AND SEC 407.1.3 |
| | 3) SHT A2.3PROVIDE CALCULATIONS FOR |
| | PRIMARY AND SECONDARY ROOF DRAINS PER |
| | SEC 1108 & 1109. ADD AREAS FROM ROOFS |
| | DRAINING ON TO ROOFS AND 1/2 OF AREA OF |
| | ALL VERTICAL WALLS. |
| | 4) SUBMIT A STORM RISER DIAGRAM. SHOW |
| | ALL PIPE SIZES AND SHOW AREA DRAINED FOR |
| | EACH DRAIN. |
| | 5) SHT A2.3 ROOF ABOVE COMPUTER ROOM/ |
| | GAME ROOM, NO SECONDARY DRAIN SHOWN. |
| | 6) SHT A6.3 DETAIL #1 W/C TO BE 1'6" TO |
| | CENTERLINE OFF WALL - SHOW ON DETAIL |
| | 7) SHT A6.3 DETAIL #2 W/C TO BE 1'6" TO |
| | CENTERLINE OFF WALL - SHOW ON DETAIL |
| | 8) SHT A6.3 DETAIL #3 ROLL IN SHOWER |
| | SHALL COMPLY WITH FIG 57 AND SECTION |
| | 4.21. SHOW DETAILS FOR CONTROL HEIGHT, |
| | SEAT PLACEMENT (ADJACENT TO CONTROLS), |
| | GRAB BARS ECT. |
| | 9) SHT FS-1.1 EQUIP SCHED. #10 WATER |
| | FILTER SHALL BE NSF APPROVED. SUBMIT |
| | MANUFACTURE INFORMATION. |
| | 10 SHT FS-1.1 EQUIP SCHED. #29 NO SANT. |
| | OR WATER SHOWN FOR THIS EQUIP. |
| | 11) SHT FS-1.2 MECH NOTES #6 IS THERE A |
| | WASH DOWN FOR HOOD? |
| | 12) SHT P-1 GREASE TRAP, CONTACT RODNEY |
| | COMPO ENVIRONMENTAL COMPLIANCE FOR SIZE- |
| | ING OF GREASE TRAP. WASTE ORD #2938-96 |
| | (561) 837-4074. |
| | 13) SHTS P-1/P-2 RPZ BACKFLOW REQUIRED |
| | ON WATER SERVICE. |
| | 14) SHT P-2 WATER RISER - VALVE REQUIRED |
| | FOR 3/4" HOT TO 3 COMP. SINK IN KITCHEN. |
| | 15) SHT P-2 WATER RISER - W/C'S IN WOMEN |
| | ROOM FED BY HOT WATER/HOT & COLD TO |
| | DOUBLE COMP SINK REVERSED. |
| | 16) SHT P-2 WATER RISER - 1" COLD OUT OF |
| | WOMENS ROOM "TO PLAY AREA" BUT SHT P-1 |
| | SHOWS IT SUPPLYING A DRINKING FOUNTAIN. |
| | PLEASE CLAIRFY. ALSO A SHUT OFF VALVE IS |
| | REQUIRED FOR THIS LINE. |
| | 17) SHT P-2 WATER RISER - 1" COLD WATER |
| | TO PLAY AREA REQUIRES A SHUT OFF VALVE, |
| | AND A BACKFLOW PREVENTER. |
| | 18) SHT P-2 GAS RISER, THE FOLLOWING IN- |
| | FORMATION IS REQUIRED FOR GAS PERMIT |
| | APPROVAL. SEPARATE GAS PERMIT REQUIRED. |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER STANDARD |
| | GAS CODE. |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | C. TYPE OF GAS, (LP OR NATURAL) |
| | D. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER STANDARD GAS CODE SEC. 305.2. IF |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | STANDARD GAS CODE SEC. 402. |
| | F). EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. |
| | 19) SHT P-3 WATER HEATER DETAIL SHOWS |
| | RELIEF LINE & PAN DRAIN DRAINING INTO A |
| | FLOOR DRAIN, BUT SHT P-1 & SHT P-2 FIX- |
| | TURE SCHED. SHOW LINES PIPED OUTSIDE- 6" |
| | ABOVE GRADE. PLEASE CLAIRFY. |
| | 20) SHT L2 WATER PLAY BY VORTEX, PUMP |
| | VAULT (FOR WATER PLAY) & ENCLOSURE BY |
| | VORTEX. - SUBMIT MANUFACTURE SHEETS AND |
| | INFORMATION WITH LISTED APPROVAL. SHOW |
| | DETAILS OF SYSTEM. SUBMIT INFORMATION TO |
| | HEALTH DEPT. FOR APPROVAL BEFORE RESUB- |
| | MITTING TO CITY FOR REVIEW. |
| | 21) SHT P-2 SANITARY RISER DIAGRAM, |
| | FLOOR DRAIN IN MENS ROOM NOT SHOWN OR |
| | RISER DIAGRAM. |
| | 22) SHT P-2 2 FLOOR DRAINS SHOWN ON SHT |
| | P-1 FLOOR PLAN AND ONLY 1 SHOWN ON RISER |
| | DIAGRAM. PLEASE CLAIRFY. |
| | |
| | REVIEW BY KEN STEVENS |