| 2002-03-28 00:00:00 | *******************DENIED*************** |
| | |
| | PLAN REVIEW UNDER 1997 SMC |
| | |
| | 1.FIRE DAMPERS REQUIRED AT WHERE DUCTS |
| | PENETRATE A WALL WITH A RATING 1 HR |
| | OR GREATER.INDICATE LOCATIONS OF |
| | ALL FIRE DAMPERS ON PLAN AS PER 1997 |
| | SMC 610.6. |
| | |
| | 2.PROVIDE OUTSIDE AIR CALCULATIONS AS |
| | PER AHSRAE 62-1989. |
| | |
| | 3.INDICATE WHERE EMERGENCY DRAIN LINE |
| | WILL TERMINATE - AS PER 1997 SMC |
| | 304.8.6.1, DRAIN LINE NOTE LESS THAN |
| | 3/4" PIPE SIZE SHALL EXTEND FROM PAN |
| | AND TERMINATE AT A CONSPICUOUS POINT |
| | TO SERVE AS AN ALARM THAT PRIMARY |
| | DRAIN IS RESTRICTED. |
| | |
| | 4.PROVIDE DETAIL FOR THE ATTACHMENT |
| | OF THE CONDENSER UNIT STAND TO THE |
| | ROOF.PLEASE NOTE AS PER COUNTWIDE |
| | AMENDMENTS, 18" MINIMUM BETWEEN THE |
| | ROOF SURFACE AND THE BOTTOM OF THE |
| | SUPPORT RAIL. |
| | |
| | 5.PROVIDE MANUFACTURER SUBMITTAL DATA |
| | FOR THE KILN. |
| | |
| | ADDITIONAL PERMITS REQUIRED FOR HOOD, |
| | FIRE SUPRESSION AND WALK-IN COOLERS OR |
| | FREEZERS.PROVIDE MANUFACTURER |
| | SUBMITTAL DATA & PLANS WITH PERMIT |
| | APPLICATION. |
| | |