| Plan Review Notes For Permit 02022214 |
| Permit Number |
02022214 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-03-04 00:00:00 | *******************DENIED*************** | | | | | | AS PER 1997 SBC 1006.1.3.1, | | | PENETRATIONS INTO AND OPENINGS THROUGH A | | | STAIRWAY ENCLOSURE ARE PROHIBITED. | | | | | | AS PER NFPA 90A 3-3.4.3, SHAFTS THAN | | | ENCLOSE AIR DUCTS SHALL NOT ENCLOSE: | | | (F) PIPING. | | | | | | CONDENSER UNIT - EQUIPMENT RAILS - | | | 18" MINIMUM BETWEEN THE ROOF SURFACE AND | | | THE BOTTOM OF THE SUPPORT RAIL AS PER | | | COUNTYWIDE AMENDMENTS 1997 SMC 304.2.5 | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|