2002-03-04 00:00:00*******************DENIED***************
  
 AS PER 1997 SBC 1006.1.3.1,
 PENETRATIONS INTO AND OPENINGS THROUGH A
 STAIRWAY ENCLOSURE ARE PROHIBITED.
  
 AS PER NFPA 90A 3-3.4.3, SHAFTS THAN
 ENCLOSE AIR DUCTS SHALL NOT ENCLOSE:
 (F) PIPING.
  
 CONDENSER UNIT - EQUIPMENT RAILS -
 18" MINIMUM BETWEEN THE ROOF SURFACE AND
 THE BOTTOM OF THE SUPPORT RAIL AS PER
 COUNTYWIDE AMENDMENTS 1997 SMC 304.2.5
  