Plan Review Notes
Plan Review Notes For Permit 02022214
Permit Number 02022214
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2002-03-01 00:00:00A) IT WAS NOTED THAT EQUIPMENT APPEARS
 TO BE RUNNING THROUGH EXIT(S). PLEASE
 BE ADVISED THAT THE ONLY PENETRATIONS
 ALLOWED ARE: ELECTRICAL CONDUIT SERVING
 THE STAIRWAY, REQUIRED EXIT DOORS,
 DUCTWORK AND EQUIPMENT NECESSARY FOR
 INDEPENDENT STAIR PRESSURIZATION, WATER
 OR STEAM PIPING FOR HEATING AND COOLING
 OF THE EXIT ENCLOSURE, SPRINKLER
 PIPING, STANDPIPES. RE: NFPA 101,
 THE LIFE SAFETY CODE, 2000 EDITION,
 SECTION 7.1.3.2.1 (E).
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910