Plan Review Notes
Plan Review Notes For Permit 02022186
Permit Number 02022186
Review Stop P
Sequence Number 2
Notes
Date Text
2002-05-17 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 11 FACBC
  
 1) FROM PREVIOUS REVIEW, PLEASE CONTACT
 RONDEY COMPO, ENVIRONMENTAL CONPLIANCE
 TO SIZE GREASE TRAP. (561) 837-4074.
 UTILITY ORDINANCE #2938-96
 2) TABLE 403.1 REQUIRED A DRINKING
 FOUNTAIN. ALSO SEE SECTION 410.1, IF A
 DRINKING COOLER IS USED IT SHALL COMPLY
 WITH ARI-1010. PLEASE SUBMIT MANUFACTURE
 INFORMATION SHEETS SHOWING COMPLIANCE.
 3) 140 DEGREE WATER REQUIRED FOR THREE
 COMPARTMENT SINK AND JANITOR MOP SINK.
 PLEASE PROVIDE TO THESE FIXTURES BEFORE
 TEMPERING WATER FOR OTHER FIXTURES.
 4) PLEASE REROUTE NEW PLANS TO DEPART-
 MENT OF BUSINESS REGULATION HOTEL AND
 RESTURANT DIVISION TO BE STAMPED BEFORE
 RESUBMITTING FOR PLAN REVIEW.
 5. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND FBC-2001
 FUEL GAS CODE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377