| Plan Review Notes For Permit 02022186 |
| Permit Number |
02022186 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-05-17 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 FUEL GAS | | | FBC-2001 CHAPTER 11 FACBC | | | | | | 1) FROM PREVIOUS REVIEW, PLEASE CONTACT | | | RONDEY COMPO, ENVIRONMENTAL CONPLIANCE | | | TO SIZE GREASE TRAP. (561) 837-4074. | | | UTILITY ORDINANCE #2938-96 | | | 2) TABLE 403.1 REQUIRED A DRINKING | | | FOUNTAIN. ALSO SEE SECTION 410.1, IF A | | | DRINKING COOLER IS USED IT SHALL COMPLY | | | WITH ARI-1010. PLEASE SUBMIT MANUFACTURE | | | INFORMATION SHEETS SHOWING COMPLIANCE. | | | 3) 140 DEGREE WATER REQUIRED FOR THREE | | | COMPARTMENT SINK AND JANITOR MOP SINK. | | | PLEASE PROVIDE TO THESE FIXTURES BEFORE | | | TEMPERING WATER FOR OTHER FIXTURES. | | | 4) PLEASE REROUTE NEW PLANS TO DEPART- | | | MENT OF BUSINESS REGULATION HOTEL AND | | | RESTURANT DIVISION TO BE STAMPED BEFORE | | | RESUBMITTING FOR PLAN REVIEW. | | | 5. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND FBC-2001 | | | FUEL GAS CODE. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|