| 2002-03-19 00:00:00 | DENIED |
| | REFERENCE: SPC-94 - FACBC-97 |
| | |
| | 1) SHT A1 (1 OF 2) CODE CLASSIFICATION |
| | #3 STANDARD PLUMBING CODE 1994 IN EFFECT |
| | NOT 1997. PLEASE CHANGE TO REFLECT PRO- |
| | PER CODE. |
| | 2) SHT A1 (1 OF 2) SPC TABLE 407 REQUIR- |
| | ES THAT 2 TOILET ROOMS, 1 FOR MALE AND |
| | 1 FOR FEMALE BE PROVIDED. |
| | 3) SHT A1 (1 OF 2) PLUMBING RISER - HUB |
| | DRAIN AT STEAM TABLE NOT APPROVED. ALL |
| | INDIRECT WASTE TO DRAIN TO FLOOR SINK. |
| | SPC SEC 804.1 |
| | 4) SHT A1 (1 OF 2) PLUMBING RISER - |
| | FLOOR SINK REQUIRED FOR WOK SINK SHALL |
| | HAVE A TRAP. (NOT SHOWN) |
| | 5) SHT A1 (1 OF 2) FLOOR DRAIN IN TOILET |
| | ROOMS SHALL HAVE TRAP PRIMER. SPC SEC |
| | 409.4.1.1 - ALL OTHER TRAPS SEALS SUB- |
| | JECT TO EVAPORATION SHALL BE OF THE DEEP |
| | SEAL TYPE NOT LESS THAN 4" WATER SEAL OR |
| | SHALL BE FED FROM A TRAP PRIMER. |
| | 6) SHT A2 (2 OF 2) MINIMUM GREASE TRAP |
| | 750 GALS. PLEASE CONTACT RODNEY COMPO, |
| | ENVRONMENTAL COMPLIANCE, (561) 837-4074 |
| | FOR GREASE TRAP SIZE. WASTE ORD #2938-96 |
| | 7) SHT A2 (2 OF 2) GREASE TRAPS INSIDE |
| | KITCHEN AREA NOT APPROVED. PLEASE REMOVE |
| | 8) SHT A2 (2 OF 2) SEPARATE SANITARY AND |
| | GREASE LINES REQUIRED. |
| | 9) SHT A2 (2 OF 2) WATER RISER DIAGRAM |
| | REQUIRED. SPC SEC 104.2.1 - AIR CHAMBERS |
| | ARE A QUICK FIX AND DO NOT WORK. IF |
| | WATER HAMMER ARRESTORS ARE USED THEY |
| | SHALL BE LOCATED NEAR THE FIXTURES IN AN |
| | EFFECTIVE RANGE AND NOT AT TOP OF DROPS. |
| | 10 SHT A2 (2 OF 2) SEPARATE GAS PERMIT |
| | REQUIRED. SEE FOLLOWING GAS PERMIT |
| | APPLICATION REQUIREMENTS. |
| | 11 SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER STANDARD |
| | GAS CODE. |
| | 12 BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE STANDARD GAS CODE SECS. 305.2 THRU |
| | 305.4 AND TABLES 305.4(A) THRU 305.4(E). |
| | 13 SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | THE STANDARD GAS CODE SEC. 305.4(I). |
| | 14 INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER STANDARD GAS CODE SEC. 305.2. IF |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | 15 SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE AND TERMINATION OF THE |
| | GAS VENTS PER THE STANDARD GAS CODE SECS |
| | 602 THRU 612. |
| | 16 SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | STANDARD GAS CODE SEC. 402. |
| | 17. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 659-8096 EXT 8377 |