Plan Review Notes
Plan Review Notes For Permit 02022186
Permit Number 02022186
Review Stop P
Sequence Number 1
Notes
Date Text
2002-03-19 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 1) SHT A1 (1 OF 2) CODE CLASSIFICATION
 #3 STANDARD PLUMBING CODE 1994 IN EFFECT
 NOT 1997. PLEASE CHANGE TO REFLECT PRO-
 PER CODE.
 2) SHT A1 (1 OF 2) SPC TABLE 407 REQUIR-
 ES THAT 2 TOILET ROOMS, 1 FOR MALE AND
 1 FOR FEMALE BE PROVIDED.
 3) SHT A1 (1 OF 2) PLUMBING RISER - HUB
 DRAIN AT STEAM TABLE NOT APPROVED. ALL
 INDIRECT WASTE TO DRAIN TO FLOOR SINK.
 SPC SEC 804.1
 4) SHT A1 (1 OF 2) PLUMBING RISER -
 FLOOR SINK REQUIRED FOR WOK SINK SHALL
 HAVE A TRAP. (NOT SHOWN)
 5) SHT A1 (1 OF 2) FLOOR DRAIN IN TOILET
 ROOMS SHALL HAVE TRAP PRIMER. SPC SEC
 409.4.1.1 - ALL OTHER TRAPS SEALS SUB-
 JECT TO EVAPORATION SHALL BE OF THE DEEP
 SEAL TYPE NOT LESS THAN 4" WATER SEAL OR
 SHALL BE FED FROM A TRAP PRIMER.
 6) SHT A2 (2 OF 2) MINIMUM GREASE TRAP
 750 GALS. PLEASE CONTACT RODNEY COMPO,
 ENVRONMENTAL COMPLIANCE, (561) 837-4074
 FOR GREASE TRAP SIZE. WASTE ORD #2938-96
 7) SHT A2 (2 OF 2) GREASE TRAPS INSIDE
 KITCHEN AREA NOT APPROVED. PLEASE REMOVE
 8) SHT A2 (2 OF 2) SEPARATE SANITARY AND
 GREASE LINES REQUIRED.
 9) SHT A2 (2 OF 2) WATER RISER DIAGRAM
 REQUIRED. SPC SEC 104.2.1 - AIR CHAMBERS
 ARE A QUICK FIX AND DO NOT WORK. IF
 WATER HAMMER ARRESTORS ARE USED THEY
 SHALL BE LOCATED NEAR THE FIXTURES IN AN
 EFFECTIVE RANGE AND NOT AT TOP OF DROPS.
 10 SHT A2 (2 OF 2) SEPARATE GAS PERMIT
 REQUIRED. SEE FOLLOWING GAS PERMIT
 APPLICATION REQUIREMENTS.
 11 SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER STANDARD
 GAS CODE.
 12 BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE STANDARD GAS CODE SECS. 305.2 THRU
 305.4 AND TABLES 305.4(A) THRU 305.4(E).
 13 SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 THE STANDARD GAS CODE SEC. 305.4(I).
 14 INDICATE THE DELIVERY PRESSURE (PSI)
 PER STANDARD GAS CODE SEC. 305.2. IF
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 15 SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER THE STANDARD GAS CODE SECS
 602 THRU 612.
 16 SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 STANDARD GAS CODE SEC. 402.
 17. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
 REVIEW BY KEN STEVENS