2002-03-20 00:00:00********************DENIED**************
  
 PLANS REVIEWED UNDER THE 2001 FBC, MECH.
  
  
 1.PROVIDE OUTSIDE AIR CALCULATIONS AS
 PER 2001 FBC, MECHANICAL 403.3.
  
 2.PROVIDE AIR BALANCE SCHEDULE SHOWING
 COMPLIANCE WITH 502.1.
  
 3.PROVIDE EQUIPMENT INFORMATION FOR
 THE HVAC SYSTEM, FAN SCHEDULE FOR
 ANY EXHAUST/AIR MAKE-UP.
  
 4.INDICATE DUCT LAYOUT, MATERIAL, SIZE
 AND CFM DISTRIBUTION.
  
 ADDITIONAL PERMITS REQUIRED FOR HOOD,
 FIRE SUPRESSION, GAS, AND WALK-IN
 COOLERS/FREEZERS.PLEASE PROVIDE PLANS
 AND MANUFACTURERS SUBMITTAL
 DATA/PRODUCT APPROVALS WITH PERMIT
 APPLICATION.
  