Plan Review Notes
Plan Review Notes For Permit 02022186
Permit Number 02022186
Review Stop E
Sequence Number 1
Notes
Date Text
2002-03-12 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE A COMPLETELY
 DIFFERENT ELECTRICAL PLAN IS NOW SUBMITT
 -ED?? THE RESPONSE SHEET FROM ARCH? SAYS
 COMMENTS WERE ADDRESSED?
  
 2)NOTE: PLEASE NOTE NO LOAD CALCUALTIONS
 , PANEL SIZE, PANEL SCHEDULE, RISER
 DIAGRAM,,,,, NEC 215-5, NEC 220.
  
 3)NOTE: PLEASE NOTE THAT ALL CIRCUIT #`S
 ARE TO BE SHOWN ON PLANS AND CORRELATE
 WITH A SUBMITTED PANEL SCHEDULE.
  
 4)NOTE: PLEASE SUBMIT AN EQUIPMENT
 SCHEDULE.
  
 5)NOTE: PLEASE NOTE THAT COVER SHEET
 REFERENCES THE 1997 NEC?? PLEASE NOTE
 THERE IS NO "97" NEC. PLEASE ALSO NOTE
 THAT WE ARE UNDER THE "99" NEC. PLEASE
 CORRECT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
 PLEASE ADDRESS ANY FIRE REVIEW COMMENTS
 THAT MAY AFFECT ELECTRICAL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372