| 2002-03-12 00:00:00 | **************** UNSAT **************** | | | | | | 1)NOTE: PLEASE NOTE A COMPLETELY | | | DIFFERENT ELECTRICAL PLAN IS NOW SUBMITT | | | -ED?? THE RESPONSE SHEET FROM ARCH? SAYS | | | COMMENTS WERE ADDRESSED? | | | | | | 2)NOTE: PLEASE NOTE NO LOAD CALCUALTIONS | | | , PANEL SIZE, PANEL SCHEDULE, RISER | | | DIAGRAM,,,,, NEC 215-5, NEC 220. | | | | | | 3)NOTE: PLEASE NOTE THAT ALL CIRCUIT #`S | | | ARE TO BE SHOWN ON PLANS AND CORRELATE | | | WITH A SUBMITTED PANEL SCHEDULE. | | | | | | 4)NOTE: PLEASE SUBMIT AN EQUIPMENT | | | SCHEDULE. | | | | | | 5)NOTE: PLEASE NOTE THAT COVER SHEET | | | REFERENCES THE 1997 NEC?? PLEASE NOTE | | | THERE IS NO "97" NEC. PLEASE ALSO NOTE | | | THAT WE ARE UNDER THE "99" NEC. PLEASE | | | CORRECT. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | PLEASE ADDRESS ANY FIRE REVIEW COMMENTS | | | THAT MAY AFFECT ELECTRICAL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|