| Plan Review Notes For Permit 02022186 |
| Permit Number |
02022186 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-03-27 00:00:00 | BUILDING PLAN REVIEW | | | ******PROVISO******* | | | ROBERT BROWN(561) 659 8096 EXT 8499 | | | | | | FBC = FLORIDA BUILDING CODE 2001 | | | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) | | | | | | --PROVISO-- | | | FBC 11-7.2(1)THE HEIGHT OF THE SALES | | | COUNTER IS NOT SHOWN.AT LEAST A 36" | | | LENGTH OF COUNTER SHALL HAVE A MAXIMUM | | | HEIGHT OF 36" ABOVE FINISHED FLOOR LEVEL | | | TO SATISFY THE REQUIREMENT FOR AN | | | ACCESSIBLE SALES COUNTER. | | | | | | --PROVISO-- | | | THE APPLICANT'S NOTE ON THE PERMIT | | | APPLICATION FORM REQUESTS THAT THE PLANS | | | BE REVIEWED FOR COMPLIANCE WITH THE | | | FLORIDA BUILDING CODE.THEREFOR, | | | SHEET A-1, 'CODE CLASSIFICATION', MUST | | | BE AMENDED TO REFER TO THE FLORIDA | | | BULDING CODE 2001, BUILDING VOLUME, | | | FUEL GAS VOLUME, MECHANICAL VOLUME AND | | | PLUMBING VOLUME. |
|