| Date |
Text |
| 2002-03-20 00:00:00 | **************** UNSAT *************** | | | | | | 1)NOTE: PLEASE NOTE THAT THERE ARE MANY | | | WHITED OUT HAND CHANGES ONPLANS. | | | PLEASE NOTE THAT THESE CHANGES NEED TO | | | BE CORRECTED BY THE ARCH/ENGINEER OF | | | RECORD PER FAC/FS 471.025/481.221. | | | PLEASE NOTE THAT LOAD CALCUALTIONS | | | NEED TO BE REVISED ALSO TO REFLECT | | | CHANGES MADE. | | | | | | 2)NOTE: PLEASE NOTE THE REQ`D EGRESS | | | LIGHTING AT REAR OF DWELLING WAS ALSO | | | WHITED OUT? PLEASE NOTE EGRESS LT(S) | | | IS REQ`D 210-70. | | | PLEASE NOTE THIS IS FOR LIBRARY ALSO. | | | | | | 3) PLEASE CLARIFY EQUIPMENT GROUNDING | | | METHOD BETWEEN FIRST MEANS OF DISCONNECT | | | AND PANEL(S). EQUIPMENT GROUNDING | | | CONDUCTORS ARE TO BE SIZED BY 250-122. | | | MISSING. | | | | | | 4)NOTE: PLEASE LIST THE REQ`D ARC FAULT | | | PROTECTED CIRCUIT(S) ON PANEL SCHEDULE | | | PER 210-12. | | | | | | | | | PLEASE SUBMIT THE ABOVE CORRECTIONS FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|