| 2002-04-09 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT #02021927 |
| | 1111 FLAGLER DR |
| | CONT: POLO HOMES OF P B INC |
| | TEL: 833-7331 |
| | CEL: 385-4400 |
| | |
| | SBC= 1997 STANDARD BUILDING CODE |
| | SBC*= AMENDMENTS STANDARD BUILDING CODE |
| | |
| | 1) A NEW NOTICE OF COMMENCEMENT WITH THE |
| | CORRECT ADDRESS. |
| | 2) PLANS DO NOT INDICATE AS TO WHICH |
| | CODE THEY WERE DESIGNED. JAN/ FEB 2002 |
| | PLANS COULD BE APPLIED FOR PERMIT DESIGN |
| | ED TO 1997 BUILDING CODE OR THE 2001 |
| | FLORIDA CODE. |
| | 3) THE DESIGNER OF RECORD SHALL INDICATE |
| | THE CODE, AND DESIGN PARAMETERS AND |
| | ASSUMPTIONS FOR THIS STRUCTURE. |
| | 4) SBC 3107 FLOOD PLAIN, TO REFER TO THE |
| | CITY CODE 12.17 THIS LOT IS PARTLY LOCAT |
| | ED IN A A-5 FLOOD PLAIN.THE REMAINDER OF |
| | THE LOT IS LOCATED IN A "B" ZONE. THE |
| | NEW STRUCTURE, IF ANY PORTION IS BUILT |
| | IN THE FLOOD ZONE THEN THE WHOLE STRUC- |
| | TURE HAS TO QUALIFY UNDER THE PROVISIONS |
| | FOR CONSTRUCTION IN FLOOD ZONES.THE |
| | ELEVATION FOR THE FINISH FLOOR ELEVATION |
| | IS NOT GIVEN. FOR FLOOD ZONE A-5 THE |
| | MINIMUM FLOOR ELEVATION FINISH FLOOR |
| | HEIGTH IS 7'-6" NGVD. NOTE ALL EXTERIOR |
| | POOL EQUIPMENT, AND A/C UNITS SHALL ALSO |
| | BE ABOVE THIS ELEVATION. THE OWNERS OF |
| | THIS SITE MAY INSIST THAT THE BUILDING |
| | BE BUILT OUTSIDE OF THE FLOOD ZONE FOR |
| | INSURANCE PURPOSES. A TIE IN SURVEY |
| | INDICATING THE FINISH FLOOR HEIGTH AND |
| | THE LOCATION OF THE A-5 ZONE IN REGARDS |
| | TO THE RELATIONSHIP OF THE BUILDING. |
| | 5) ENERGY EFFICIENCY SHEET NOT SIGNED BY |
| | THE OWNER OR HIS AGENT OR THE CONTRACTOR |
| | 6) FL STATE STATUTE61G15-23.002 ENGINEER |
| | TO SEAL ALL DOCUMENTS THAT ARE FOR PUB- |
| | LICRECORD (SOILS REPORT). |
| | 7) SBC TABLE 500 INDICTES THAT A TYPE VI |
| | BUILDING UNPROTECTED CAN BE 2 STORIES, |
| | THE GAME ROOM CONSTITUTES A THIRD STORY, |
| | THIS WOULD MEAN FOR TYPE VI BUILDING |
| | 1 HR PROTECTED WOULD ALLOW FOR A THIRD |
| | STORY. ALL STRUCTURAL ELEMENTS WOULD BE |
| | 1 HR PROTECTED. INDICATE FLOOR/CEILING |
| | ASSEMBLY #'SEITHER UL OR GYPSUM ASSOC. |
| | |
| | 8) 1606.2.6.2 COMPONENTS & CLADDING, ALL |
| | PRODUCT TESTING REPORTS REQUIRE 2 COPIES |
| | SBCCI OR DADE COUNTY REPORTS ARE ACCEPT- |
| | ED. ALL GLAZED OPENINGS REQUIRE LARGE |
| | MISSLE RESISTANCE TESTING FOR WINDOWS, |
| | DOORS AND SKYLIGHTS. IF THE GLAZED UNIT |
| | HAS NOT BEEN TESTED, THEN STORM SHUTTERS |
| | SHALL BE REQUIRED. |
| | THE FRONT DOOR MISSING REPORT. |
| | GARAGE DOORS: RAYNOR INDICATE AS TO |
| | WHICH MODEL SHALL BE USED? |
| | OUTSWING CASEMENT WINDOWS, REPORT HAS |
| | EXPIRED 1-28-02 |
| | MULLION REPORT SHEET FOR CHART ILLEGABLE |
| | TO SMALL, REPORT EXPIRED |
| | STORM SHUTTERS: MISSING REPORT, NOT ON |
| | A-7 FOR STORM SHUTTERS. |
| | 9) SHEET A-2 INDICATES 2,111 SQ FT. |
| | SBC 2305.2.2DRAFTSTOPPING EVERY 500 SQ |
| | FT OR EVERY PART THERE OF. |
| | 10) SHEETS-5 DETAIL #3 FLOOR TRUSSES |
| | SHALL REQUIRE A FIRE CUT SBC 2305.4. |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | (561)659-8096 X 8412 |