| 2002-04-17 00:00:00 | ************* UNSAT ****************** |
| | |
| | 1) NOTE: PLEASE SHOW ALL OUTLETS SERVING |
| | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| | -ED PER 210-8-A-6. |
| | INCLUDES KITCHEN ISLANDS. |
| | |
| | 2 )NOTE: PLEASE NOTE KITCHEN COUNTER- |
| | -SPACE RECEPT SPACING SHALL MEET ART; |
| | 210-52C 1,2,3,4,AND 5. |
| | MISSING COUNTER AND PENINSULARS. |
| | |
| | 3) NOTE: PLEASE SHOW GROUNDING ELECTRODE |
| | GOING TO BUILDING STEEL AND COLD WATER |
| | PER 250-50. SIZE PER 250-66 |
| | |
| | 4)NOTE: PLEASE NOTE THAT SD ON LOWER |
| | LEVEL SHALL BE MOUNTED IN CLOSE |
| | PROXIMITY TO THE STAIRWAY LEADING TO THE |
| | FLOOR ABOVE. NFPA-72 2-5.2.1.3. SHOW |
| | |
| | 5)NOTE: PLEASE NOTE MISSING BATH GFI |
| | IN LOWER BATHROOM PER 210-52D. |
| | |
| | 6)NOTE: PLEASE NOTE MISSING OUTLET FOR |
| | A/C EQUIPMENT. PER 210-63 AND/OR SECTION |
| | 306 OF THE MECHANICAL CODE. |
| | |
| | 7)NOTE: PLEASE NOTE THAT AHU#3 IS NOT |
| | SHOWN? PLEASE CLARIFY. COND UNIT#3 IS |
| | SHOWN ,BUT NOT AHU. |
| | PLEASE SHOW/CLARIFYDISC`S NOT SHOWN |
| | PER 440-11. |
| | |
| | 8)NOTE: PLEASE NOTE THAT GARAGR OUTLET |
| | IS TO BE SHOWN AS GFI/GFI PROTECTED, |
| | 210-8 |
| | |
| | 9)NOTE: PLEASE NOTE/CLARIFY REQ`ED MEANS |
| | OF EGRESS LIGHTING FOR HALL/STAIRWAY. |
| | SHOWN AS "J"-BOX ONLY. PLEASE SEE OTHER |
| | HALLS, HABITABLE ROOMS ANDBACK PORCH. |
| | 210-70 |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |