| 2002-07-18 00:00:00 | BUILDING PLAN REVIEW |
| | *******PROVISO****** |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |
| | |
| | --PROVISO-- |
| | IMPACT FEES SHALL BE PAID TO PALM BEACH |
| | COUNTY (FOR INFO, TEL: 561 233 5115) |
| | |
| | --PROVISO-- |
| | A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT SHALL BE SUBMITTED. |
| | |
| | --PROVISO-- |
| | FL ENERGY CODE 103.0THE SUBMITTED |
| | ENERGY CODE COMPLIANCE FORM SHALL BE |
| | COMPLETED BY ENTERING THE FOLLOWING INFO |
| | PERMITTING OFFICE: WEST PALM BEACH |
| | JURISDICTION NO.: 604700 |
| | THE CORRECT PERMIT NUMBER IS 02021913 |
| | |
| | --PROVISO-- |
| | SBC* 1606.4SUBMIT PRODUCT APPROVALS |
| | FOR THE EXTERNAL DOORS AND WINDOWS. |
| | |
| | --PROVISO-- |
| | SUBMIT PRODUCT APPROVALS FOR THE ROOFING |
| | MATERIALS.NO PRODUCT APPROVAL HAS BEEN |
| | SUBMITTED FOR THE ASPHALT SHINGLES |
| | PROPOSED FOR THE PITCHED ROOF.ALSO, |
| | THE SUBMITTED BUILT-UP ROOFING PRODUCT |
| | APPROVAL FOR THE FLAT ROOF IS INCOMPLETE |
| | SUBMIT ALL OF THE SHEETS (STAMPED BY THE |
| | MIAMI-DADE PRODUCT EXAMINER) APPLICABLE |
| | TO THIS INSTALLATION. |
| | |
| | --PROVISO-- |
| | SHEET 2, TYPICAL SECTION, HAS BEEN |
| | RED-LINED TO SHOW A GROUTED CELL AT EACH |
| | STEM WALL REINFORCEMENT LOCATION AND TO |
| | SHOW THE STEM WALL REINFORCEMENT AS |
| | HAVING THE REQUIRED STANDARD HOOK INTO |
| | THE CMU BOND BEAM. |