| Plan Review Notes For Permit 02021913 |
| Permit Number |
02021913 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-03-06 00:00:00 | ***************** UNSAT *************** | | | | | | 1)NOTE: PLEASE CLARIFY, PLANS ARE SHOW- | | | -ING A NEW PANEL IN HALL? PLEASE SHOW/ | | | OR PROVIDE DETAIL WHERE/HOW THIS PANEL | | | IS BEING FED. | | | | | | 2)NOTE: PLEASE NOTE THAT PLANS SHOW | | | NEW WASHER/DRYER/WATER HEATER, PLEASE | | | CLARIFY IF THESE ARE NEW ADDED LOADS TO | | | EXISITNG SERVICE OR ARE THESE BEING | | | MOVED FROM EXSITING LOCATION? | | | IF NEW/ADDED, PLEASE PROVIDE LOAD CALCU- | | | -LATIONS FOR SERVICE AND SHOW SIZE OF | | | SERVICE. | | | | | | 3) NOTE: PLEASE LIST THE REQ`D BATH(S) | | | CIRCUIT(S) PER 210-11-C-3. | | | MUST BE 20A AND #12AWG. | | | | | | 4)NOTE: PLEASE NOTE, A SMOKE DETECTOR IS | | | REQ`D. THIS IS AN ADAPTABLE BEDROOM W/ | | | THE CLOSET AND OR BATH ATTACHED. | | | | | | 5)NOTE: PLEASE ALSO NOTE THAT PLANS | | | SHOW A J.B. IN THE MIDDLE OF THE FAM RM, | | | PLEASE NOTE A LT FIXTURE IS REQ`D FOR | | | EGRESS. 210-70 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|