Plan Review Notes
Plan Review Notes For Permit 02021913
Permit Number 02021913
Review Stop E
Sequence Number 1
Notes
Date Text
2002-03-06 00:00:00***************** UNSAT ***************
  
 1)NOTE: PLEASE CLARIFY, PLANS ARE SHOW-
 -ING A NEW PANEL IN HALL? PLEASE SHOW/
 OR PROVIDE DETAIL WHERE/HOW THIS PANEL
 IS BEING FED.
  
 2)NOTE: PLEASE NOTE THAT PLANS SHOW
 NEW WASHER/DRYER/WATER HEATER, PLEASE
 CLARIFY IF THESE ARE NEW ADDED LOADS TO
 EXISITNG SERVICE OR ARE THESE BEING
 MOVED FROM EXSITING LOCATION?
 IF NEW/ADDED, PLEASE PROVIDE LOAD CALCU-
 -LATIONS FOR SERVICE AND SHOW SIZE OF
 SERVICE.
  
 3) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 4)NOTE: PLEASE NOTE, A SMOKE DETECTOR IS
 REQ`D. THIS IS AN ADAPTABLE BEDROOM W/
 THE CLOSET AND OR BATH ATTACHED.
  
 5)NOTE: PLEASE ALSO NOTE THAT PLANS
 SHOW A J.B. IN THE MIDDLE OF THE FAM RM,
 PLEASE NOTE A LT FIXTURE IS REQ`D FOR
 EGRESS. 210-70
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372