Plan Review Notes
Plan Review Notes For Permit 02021913
Permit Number 02021913
Review Stop B
Sequence Number 1
Notes
Date Text
2002-03-26 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 SBC = STANDARD BUILDING CODE 1997
 SBC*= STANDARD BUILD'G CODE (CITY AMEND)
 FL ENERGY CODE = FLORIDA ENERGY
 EFFICIENCY CODE FOR BUILD'G CONSTR'N
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) FL ENERGY CODE 103.0COMPLIANCE
 SHALL BE DEMONSTRATED BY SUBMITTAL OF
 APPROPRIATE ENERGY CODE COMPLIANCE FORMS
 FOR THE ADDITION
 (REF: FL ENERGY CODE 600.2.A.3)
  
 4) SBC* 1606.4BUCK CONNECTIONS FOR
 EXTERNAL DOORS AND WINDOWS.SUBMIT
 PRODUCT APPROVALS.
  
 5) SBC 1606.3.2ROOF COVERING FOR THE
 FLAT AND PITCHED ROOFS.SUBMIT PRODUCT
 APPROVALS OR A SEPARATE ROOFING PERMIT
 APPLICATION WILL BE REQUIRED.
  
 6) SBC 2303.2SHEET 2, TYPICAL SECTION.
 THE CMU BOND BEAM IS NOT ADEQUATELY
 ANCHORED.IT SHALL BE TIED TO THE
 FOUNDATION USING #5 STEM WALL
 REINFORCEMENT AT MAX 8'-0" O.C. IN A
 GROUTED CELL, WITH A STANDARD HOOK INTO
 THE BOND BEAM (REF: SSTD 10-99, FIGURES
 303A AND 303B).
  
 7) SBC 2306SHEET 2, TYPICAL SECTION
 AND SHEET 1, GENERAL NOTE 10.THE
 PROPOSED LSTA 18 STRAP ON THE RAFTER HAS
 6-10D NAILS TO EACH EXTERIOR WALL STUD
 AND THE PROPOSED HETA 20 CONNECTOR CAST
 INTO THE CMU BOND BEAM HAS 4-10D NAILS
 INTO EACH EXTERIOR WALL STUD.WITH
 REFERENCE TO THE MANUFACTURER'S DATA, IT
 IS CONSIDERED THAT NEITHER OF THESE
 NAILING ARRANGEMENTS WILL GIVE THE
 UPLIFT CAPACITY THAT WOULD BE REQUIRED
 BY SSTD 10-99 TABLE 305F1.EITHER SHOW
 THE DERIVED UPLIFT ON THE PLANS OR
 REVISE THE DETAILS TO GIVE GREATER
 UPLIFT CAPACITY.
  
 8) SBC 2304.3THE CRAWL SPACE
 VENTILATION FOR THE EXISTING BUILDING
 SHALL BE RETAINED.
  
 9) FBC 2405.2THE SHOWER WINDOW GLASS
 IS IN A 'HAZARDOUS LOCATION' AND IS
 REQUIRED TO BE SAFETY GLASS SATISFYING
 THE REQUIREMENTS OF THE CONSUMER PRODUCT
 SAFETY COMMISSION 16, CODE OF FEDERAL
 REGULATIONS, PART 1201 (CPSC 16-CFR,
 PART 1201).AMEND THE WINDOW SCHEDULE
 TO DEMONSTRATE COMPLIANCE.
  
 10) SBC 1007.3.1STAIRWAYS.ANNOTATE
 THE PLANS TO SHOW THAT THE RISER HEIGHT
 (R) DOES NOT EXCEED 7-3/4", THE TREAD
 DEPTH (T) IS NOT LESS THAN 9" AND THE
 RELATIONSHIP 2R+T IS NOT LESS THAN 24"
 NOR MORE THAN 25".
  
 11) SHEET 1, FLOOR PLAN. THE SECTION A-A
 MARKER SHOULD READ B-B AND VICE VERSA TO
 CORRESPOND WITH THE CORRECT DETAILS ON
 SHEET 2.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUERIES PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499